107
–
'18 • KX-SM-292
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E45
E45-1
Communication error between
inverter PCB and outdoor unit control PCB
Keeps flashing Stays Off
Keeps flashing 1 time
fl
ash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is 15V
of power for control PCB
detected? Is the outdoor fan motor OK?
(Refer the checking method of 15V
in page 63)
Turn off the power.
IS the harness and/or
connector between inverter
PCB and outdoor unit control
PCB OK ?
Is the rush
current prevention resistor
broken?
Is the
harness and/or connector
between
inverter PCB and diode module
OK?
Is the
setting of switches on the inverter
PCB OK? *
Reset power source and restart
Does E45 recur?
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
Save data for 30 minutes before stopping in Mente PC
* Switch setting of inverter PCB
SW1-1
SW1-2
SW1-3
SW1-4
JSW1-1
JSW1-2
JSW1-3
JSW1-4
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
Check and save the data of
operating conditions.
Replace inverter PCB or
outdoor fan motor.
Check it as much as
possible under the operating
conditions for 30 minutes
before error occurred.
Wait and see.
Continue to obain data, if
possible (Keep connecting
the Mente PC).
Check whether the harness
is broken?
Check whether the
connector is loose?
If there is problem,
correct it.
Disconnect the harness
from the resistor and
measure the resistance.
If broken, replace the
resistor.
In such case check the
harness between diode
module and inverter PCB
as well.
Check whether the harness
is broken?
Check whether the
connector is loose?
If there is problem,
correct it.
Correct the setting of
switches on the inverter
PCB.
Replace outdoor unit control
PCB.
2. Error detection method
When the communication
between inverter PCB and
outdoor unit control PCB is not
established.
3. Condition of error displayed
Same as above
4. Presumable cause
• Signal wire anomaly
• Outdoor unit control PCB
anomaly
• Inverter PCB (INV1)
anomaly
• Rush current prevention
resistor anomaly
Note: If the error does not recur, connect the Mente PC and continue to collect data.
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E46
E46
Mixed address setting methods
coexistent in same network.
Keeps flashing Stays Off
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
NO
Reset power source and restart
If signal line is connected to more than
2 outdoor unit systems, address setting
should be done by manually.
YES
Is't the
signal line of a outdoor
unit system applying automatic
address setting connected to
other outdoor unit
system?
YES
NO
Does E46 recur?
YES
Turn ON the power of each outdoor unit
one by one and search the outdoor unit
that can start up with automatic address
setting
NO
Is E46 still displayed?
Save data for 30 minutes before stopping in Mente PC
Check and save the data of
operating conditions.
Check the address setting
method of faulty network
whether it is automatic
setting or manual setting.
Test run.
* No action is taken
because it is judged that
the power rest is not done
after changing address.
Correct signal line.
*In case of automatic
address setting, signal line
cannot be connected to
other outdoor unit system.
Test run
Replace outdoor unit control
PCB*.
(Rotary switch anomaly)
* Before replacement,
please confirm whethe
the rotary switch for
address setting is not
damaged.
(It was experienced that
No.5 on rotary switch
was not recognized.)
2. Error detection method
If the signal line of a outdoor
unit system applied automatic
address setting is connected to
other outdoor unit system
(Detected at indoor unit side)
3. Condition of error displayed
Same as above
4. Presumable cause
• Mistake in the address setting
• Mistake in the connection of
signal wire
Note:
After completing the above procedure, reset the power and confirm that the error display does not recur. Unless the power
is reset for both indoor unit and outdoor unit, the set addresses will not be confirmed
Caution:
Unless the power is reset after changing
address, the set address will not be
confirmed.
<Reference>
Error display at mixed address setting
Auto
Manual
Auto address setting
E31
E46
Manual address setting
E46
Normal