'18 • KX-SM-292
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E48
E48-1, 2 *1
Outdoor unit DC fan motor anomaly
Keeps flashing Stays Off
Keeps flashing
*1
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is 15V
of power for control PCB
detected? Is the outdoor fan motor
OK? (Refer the checking method of
15V
in page 63)
Does the
fan rotate smoothly when turned
by hand?
NO
NO
NO
NO
YES
Is E48
restored at 10 seconds after
compressor starting?
Interchange the connectors of fan motor
harnesses at the connectors on outdoor
unit control PCB side
Is the
fan motor failed to start up
switched?
Start operation again
Turn the power source OFF
Reset power source and restart
Save data for 30 minutes before stopping in Mente PC
Check and save the data of
operating conditions.
Replace fan motor.
Replace inverter PCB
or fan motor.
Check it as much as
possible under the
operating conditions for
30 minutes before error
occurred.
Wait and see.
Continue to obain data, if
possible.
(Keep connecting the
Mente PC)
Replace fan motor.
Replace outdoor unit control
PCB.
2. Error detection method
• If 400min
-1
or lower of the
fan rotation command and the
state of overcurent are detected
for 10 times continueously
• If 100min
-1
of the actual fan
rotation speed is detected for
30 seconds
(Fan motor is locked)
3. Condition of error displayed
Same as above
4. Presumable cause
• Breakage of harness
or loose conection of
connector
• Outdoor fan motor anomaly
• Inverter PCB anomaly
• Outdoor unit control PCB
anomaly
Note:
If the error does not recur, connect the Mente PC and continue to collect data.
*1 E48-1: 1 time flash (FMO1), E48-2 : 2 time flash (FMO2)
Inspect also the fan motor 2 even if it is E48-1.
Inspect also the fan motor 1 even if it is E48-2.
(
)
YES
YES
YES
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E49
E49
Low pressure anomaly
Keeps flashing Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Does the low
pressure fluctuate after the
startup?
Is the
connection of sensor connector
OK?
Does the
error occur immediately after
the startup?
Are the
sensor characteristics
OK?*
* The sensor
characteristics is shown in
Page 111
Save data for 30 minutes before stopping in Mente PC
Reset power source and restart.
Is the opening
degree of EEV
for evaporator side
flucturing?
Is the
connection of
sensor connector for
heat exchanger
OK?
Is the checked
result of harness and insulation
of EEV coil OK?
Are the sensor
characteristics OK?
Does the
EEV operate
normally by judging
from Mente PC
data, etc?
Isn’t EEV
or strainer
clogged?
Check and save the data of
operating conditions.
Check error status.
Is the refrigerant amount
OK?
Check additional
refrigerant amount charged
at site according to the
piping length instructed
on the label pasted on the
panel of the unit.
Check whether the service
valves are open.
Correct the connection
of low pressure sensor
connector.
Replace low pressure
sensor.
Replace outdoor umit control
PCB.
Correct the connection of
temperature sensor
connector of heat
exchanger.
Replace temperature
sensor of heat exchanger
at evaporator side.
Replace control PCB at
evaporator side.
Replace EEV coil.
Replace EEV main body or
strainer.
Check for short circuit of
airflow of heat exchanger
at evaporator side and for
fan motor anomaly.
2. Error detection method
Detection of anomalously low
pressure
3. Condition of error displayed
• At start up after power on:
When the low pressure sensor
detects lower than 0.003MPa
for 60 seconds continuously.
And if this anomaly occurs 2
times.
• During operation:
When the low pressure sensor
detects 0.134MPa or lower
for 30 seconds coninuously.
And if this anomaly occurs 5
times within 60 minutes
4. Presumable cause
• Low pressure sensor (PSL)
anomaly
• Service valves closed
• EEV anomaly (EEV closed)
• Insufficient refrigerant
amount
• Clogging at EEV or strainer
Note:
Check whether the indoor unit is connected to other outdoor superlink network.
If the error does not recur, connect the Mente PC and continue to collect data.
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES