116
–
'18 • KX-SM-292
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E63
E63
Emergency stop
Keeps flashing Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Indoor unit
Diagnosis
Countermeasure
Is the
remote control setting
of Emergency Stop
"Valid"?
Is ON
signal inputted to the
CnT terminal of indoor
unit control PCB?
Save data for 30 minutes before stopping in Mente PC
NO
NO
YES
Check and save the data of
operating conditions.
Check the conditions
whether it occurs
immediately after the power
on or during operation.
Replace remote control
PCB.
Replace indoor unit control
PCB.
Check the cause of
emergency stop.
(It is better to have the data
for 30 minutes before
stopping, when instructing
the installer.)
2. Error detection method
When ON signal is inputted
to the CnT terminal of indoor
unit control PCB
3. Condition of error displayed
Same as above
4. Presumable cause
Factors for emergency stop
Note:
Indoor unit detected emergency stop signal gives command "all stop"
YES
2.4 Outdoor unit control PCB replacement procedure
(Note) If cut the tie, the wiring cables should be bound with new tie again.
●
Exchange the control PCB according to the following procedure.
①
Replace the control PCB after elapsing 3 minutes from power OFF.
(Be sure to measure voltage (DC) at both capacitor terminals (1. Power source for PCB 2. Power source for fan motor)
and check that the voltage is discharged completely. (Refer to Fig.1))
②
Disconnect the connectors from the PCB.
③
Disconnect the blue wiring passing through CT1 on the PCB before replace the coutrol PCB.
④
Set the setting switches (SW1-6) and jumper wires (J11-16) of new PCB same as previous PCB.
⑤
Tighten up a screw after passing blue wiring through CT1 of the changed.
⑥
Connect the connectors to the PCB. (Contirm the connectors are not half inserted.)
After elapsing 3 minutes
from power OFF
CNQ3 2
CT1
LED2
(Green)
CNN2
CNTH
CNEEV1
CNN9
CNI
only FDC335KXZME1
CNL1
CNFAN_2
CNR1
CNB2
CNEEV2
CNQ1
CNFAN_1
CNN6
CNW
SW3-6
CNM1
CNN1
SW1,2
J11-16
Parts arrangement view
1 Reuse the parts used before the PCB exchange.
2 Please do not carry out wrong insertion.
The PCB will be destroyed if a mistake is made
in putting CNA2 (brown) and CNQ3 (yellow).
CNA2
CNQ3
LED3
(Green)
LED1
(Red)
CNA2 2
CN 2
CNS1
CNS2
CNG1
CNG2
CNX1
CNU1
CNF2
CNF1
CNP1
Precautions for Safety
●
Since the following precaution is the important contents for safety, be sure to observe them.
WARNING and CAUTION are described as follows:
Indicates an imminently hazardous situation which will result in death or serious injury if
proper safety procedures and instructions are not adhered to.
Indicates a potentially hazardous situation which may result in minor or moderate injury
if proper safety procedures and instructions are not adhered to.
WARNING
●
Securely replace PCB according to this following instruction.
If PCB is incorrectly replace, it will cause an electric shock or fire.
●
Be sure to check that the power source for the outdoor unit is turned OFF before replace PCB,
The PCB replacement under current-carrying will cause an electric shock.
●
After finishing PCB replacement, check that wiring is correctly connected with the PCB before power
distribution, If PCB is incorrectly replace, it will cause an electric shock or fire.
CAUTION
●
Bundle the wiring so as not to tense because it will cause an electric shock.
WARNING
CAUTION
L
PCB012D017G
134