119
–
'18 • KX-SM-292
Appearance of the controller
PCB voltage measurement point
(between F1, DS1(-))
Target PCB
Fan motor voltage measurement point
(between L63, L64)
Fig.1 Voltage measurement points
2.5 Inverter PCB replacement procedure
(Note) If cut the tie, the wiring cables should be bound with new tie again.
Exchange the inverter PCB according to the following procedure.
①
Replace the inverter PCB after elapsing 3 minutes from power OFF.
(Be sure to measure voltage (DC) of two places (1. Power source for PCB 2. Power source for fan motor) and check
that the voltage is discharged completely. (Refer to Fig.1))
②
Disconnect all of terminals and connectors from the inverter PCB before replace the invertor PCB.
③
Replace to the new PCB.
④
Set the setting switches (JSW 10, 11) of new PCB as shown in table 1.
⑤
Connect all of terminals and connectors to the new PCB securely.
(Check the secure connection of terminals and connectors again)
WARNING
CAUTION
Connectors are not
half inserted
After elapsing 3 minutes
from power OFF
Table.1 Switch Setting
Parts Arrangement View
CNA
CNI2
LED1
(Yellow)
CNR
JSW10,11
JSW10
1 2 3 4
JSW11
Model
All models
all OFF OFF
OFF
ON
OFF
Precautions for Safety
Since the following precaution is the important contents for safety, be sure to observe them.
WARNING and CAUTION are described as follows:
Indicates an imminently hazardous situation which will result in death or serious injury if
proper safety procedures and instructions are not adhered to.
Indicates a potentially hazardous situation which may result in minor or moderate injury
if proper safety procedures and instructions are not adhered to.
WARNING
●
●
●
●
●
●
Securely replace PCB according to this following instruction.
If PCB is incorrectly replace, it will cause an electric shock or fire.
Be sure to check that the power source for the outdoor unit is turned OFF before replace PCB,
The PCB replacement under current-carrying will cause an electric shock.
After finishing PCB replacement, check that wiring is correctly connected with the PCB before power
distribution, If PCB is incorrectly replace, it will cause an electric shock or fire.
CAUTION
Bundle the wiring so as not to tense because it will cause an electric shock.
K
PCB012D018AB
2.5 Inverter PCB replacement procedure
Summary of Contents for FDC224KXZME1
Page 169: ... 168 18 KX SM 292 PHA012D402 ...
Page 170: ... 169 18 KX SM 292 Screw ...
Page 171: ... 170 18 KX SM 292 ...
Page 172: ... 171 18 KX SM 292 ...