125
–
'18 • KX-SM-292
Pressure switch setting value
Solenoid valve operation
Name
Setting value
High pressure switch (63H
1-1
)
[For protection]
4.15 open/3.15 close (MPa)
Name
Control content
SV6
SV1
At inverter
compressor
start
: Open
During under-dome temperature control : Open
During discharge temperature control : Open
Sensor (Tho-D1)
Sensor (Tho-A)
Sensor (Tho-R1, R2)
Sensor (Tho-S)
Sensor (Tho-SC)
Sensor (Tho-H)
Sensor (Tho-C1)
: For control of discharge pipe temperature
: For heating and cooling to low outdoor temperature, for control of defrost operation
: For control of defrost operation
: For control of suction pipe temperature
: Sub-cooling coil control during cooling
: Sub-cooling coil control during cooling
: Under-dome temperature control
Function of sensor
Low pressure sensor (PSL)
High pressure sensor (PSH)
Temperature sensor
(Thi-R1,R2)
(Thi-R3)
: Compressor control
Protection
0.18 ON/0.236 OFF (MPa)
Error
0.134 ON/0.18 OFF (MPa)
: Compressor control
Protection
Cooling : 3.70 ON (MPa)
Heating : 3.00 ON (MPa)
: Heating operation
: Indoor fan control
Cooling operation
: Frost prevention
Superheat control
: Cooling superheat control
Gas piping
Check valve
4-way switching solenoid
Service valve
Service valve
Liquid piping
ø9.52
Stepping motor
(for electronic expansion valve)
Stepping motor
(for electronic expansion valve)
To next unit by turn
Strainer
Strainer
Strainer
Strainer
Strainer
Sub-cooling coi
l
Sub-cooling coil
Temperature sensor (Outlet)
(
Thi
-R3)
Temperature sensor (Return air)
(
Thi
-A)
(Tho-SC)
(EEVSC)
(Tho-C1)
(Tho-D1)
(63H1-1)
(PSH)
SV1
Temperature sensor (Inlet)
(
Thi
-R2)
Temperature sensor (Outlet)
(
Thi
-R3)
Temperature sensor (Return air)
(
Thi
-A)
Temperature sensor (Inlet)
(
Thi
-R2)
Temperature sensor (Heat exchanger)
(
Thi
-R1)
(
Thi
-R1)
Oil
separator
Temperature sensor (Heat exchanger)
Outdoor unit
Strainer
Strainer
Receiver
Super-cooling coil temperature sensor 1
Sub-cooling coil
Super-cooling coil expansion valve
Fusible plug
Under-dome temperature sensor
SV6
Capillary
tube
Discharge pipe
temperature sensor
(PSL)
Low pressure sensor
(THo-S)
Suction pipe temperature sensor
High pressure switch
Check joint
High pressure sensor
Capillary tube
(Tho-H)
Super-cooling coil temperature sensor 2
Solenoid valve (
fluid return
)
Heat exchange
r
Heat exchanger
Check joint
(Tho-A)
(Tho-R1)
Heat exchanger temperature sensor 1
(Tho-R2)
Heat exchanger temperature sensor 2
External air temperature sensor
Accumulator
Strainer
224: ø19.05
280: ø22.22
Heat exchanger
Heat exchanger
Heating expansion valve
(EEVH)
Strainer
Strainer
Coolin
g
Heating
Indoor unit A
Indoor unit B
Compressor
accumulator
(
oil return
)
Solenoid valve
(
)
4. PIPING SYSTEM
Model FDC224KXZME1, 280KXZME1