(c) Fan control during heating thermostat OFF
(i) Following fan controls during the heating thermostat OFF can be selected with the indoor function setting of the wired
remote control.
①
Low
fan speed
(Factory default),
②
Set fan speed,
③
Intermittence,
④
Fan OFF
(ii) When the “Low fan speed (Factory default)” is selected, the following taps are used for the indoor fans.
・ For DC motor : ULo tap
(iii) When the “Set fan speed” is selected, it is operated with the set fan speed also in the thermostat OFF condition.
(iv) If the “Intermittence” is selected, following controls are performed:
1) If the thermostat is turned OFF during the heating operation, the indoor fan stops.
2) Indoor fan OFF is fixed for 5 minutes. After the 5 minutes, the indoor fan is operated at ULo for 2 minutes. In the
meantime the louver is controlled at level.
3) After operating at ULo for 2 minutes, the indoor fan moves to the state of 1) above.
4) If the thermostat is turned ON, it moves to the hot start control.
5) When the heating thermostat is turned OFF, the remote control displays the temperature detected at the fan stop
and revises the temperature later when the indoor fan changes from ULo to stop.
The remote control uses the operation data display function to display temperatures and updates values of
temperature even when the indoor fan is turned OFF.
6) When the defrost operation starts while the heating thermostat is turned OFF or the thermostat is turned OFF
during defrost operation, the indoor fan is turned OFF. (Hot keep or hot start control takes priority.) However, the
suction temperature is updated at every 7-minute.
7) When the heating thermostat is turned ON or the operation is changed to another mode (including stop), this
control is stopped immediately, and the operating condition is restored.
(v) When the “Fan OFF” is selected, the fan on the indoor unit of which the thermostat has been turned OFF, is turned OFF.
The same occurs also when the remote control sensor is effective.
(d) Fan control during cooling thermostat OFF (Except FDTC, FDTQ, FDUT15-56, FDUH, FDK, FDFW,
FDFL,
FDFU)
(i) Following fan controls during the cooling thermostat OFF can be selected with the indoor function setting of the wired
remote control.
①
Low
fan speed
,
②
Set fan speed (Factory default),
③
Intermittence,
④
Fan OFF
(ii) When the “Low fan speed” is selected, the following taps are used for the indoor fans.
・ For DC motor : ULo tap
(iii) When the “Set fan speed” is selected, it is operated with the set fan speed also in the thermostat OFF condition.
(iv) If the “Intermittence” is selected, following controls are performed:
1) If the thermostat is turned OFF during the cooling operation, the indoor fan stops.
2) Indoor fan OFF is fixed for 5 minutes. After the 5 minutes, the indoor fan is operated at ULo for 2 minutes.
3) After operating at ULo for 2 minutes, the indoor fan moves to the state of 1) above.
4) If the thermostat is turned ON, the fan starts operation at set fan speed.
5) When the cooling thermostat is turned OFF, the remote control displays the temperature detected at the fan stop
and revises the temperature later when the indoor fan changes from ULo to stop.
By using operation data display function at wireless remote control, the temperature as displayad and the value is
updated including the fan stops.
6) When the cooling thermostat is turned ON or the operation is changed to another mode (including stop), this
control is stopped immediately, and the operating condition is restored.
(v) When the “Fan OFF” is selected, the fan on the indoor unit of which the thermostat has been turned OFF, is turned OFF.
The same occurs also when the remote control sensor is effective.