15
–
'18 • KX-SM-292
(8) Filter sign
As the operation time (Total ON time of ON/OFF switch) accumulates to 180 hours
(1)
, “FILTER CLEANING” is displayed
on the remote control. (This is displayed when the unit is in trouble and under the central control, regardless of ON/OFF)
Notes (1) Time setting for the filter sign can be made as shown below using the indoor function of wired remote control “Filter sign”. (It is set at Setting 1
at the shipping from factory.)
Filter sign setting
Setting 1
Setting 2
Setting 3
Setting 4
Function
Setting time: 180 h (Factory default)
Setting time: 600 h
Setting time: 1,000 h
Setting time: 1,000 h (Unit stop)
(2)
(2) After the setting time has elapsed, the “FILTER CLEANING” is displayed and, after operating for 24 hours further (counted also during the stop),
the unit stops.
(9) Compressor inching prevention control
(a) Once the indoor unit thermostat has been turned ON, the thermostat is not turned OFF for 2 minutes (*1) after the
compressor ON even if the thermostat is turned OFF at the state of item (7).
Thermostat ON/OFF with this control
2 minutes
2 minutes
OFF
ON
ON
ON
Stopped by remote control, etc.
*
1
*
1
Even when the thermostat of another indoor
unit is turned ON after the compressor ON,
the thermostat is not turned OFF for 2 minutes
after the compressor ON.
*
1
OFF
OFF
3 minutes delay
Thermostat OFF in the condition of item (7)
Compressor
Indoor unit A
Thermostat
Indoor unit B
Thermostat
(b) When the oil return control has started while the thermostat is turned ON, the thermostat is not turned OFF even if the
thermostat OFF condition is satisfied during the oil return control.
(10) Drain pump control (Except FDK)
(a) This control is operated when the inverter frequency is other than 0 Hz during the cooling operation and automatic
cooling and dehumidifying operations.
(b) Drain pump ON condition continues for 5 minutes even when it enters the OFF range according to (i) above after
turning the drain pump ON, and then stops. The 5 minutes delay continues also in the event of anomalous stop.
(c) The drain pump is operated with the 5 minutes delay operation when the compressor is changed from ON to OFF.
(d) Even in conditions other than the above (such as heating, fan, stop, cooling thermostat OFF), the drain pump control is
performed by the drain detection.
(e) Following settings can be made using the indoor function setting of the wired remote control.
(i)
ࠝ
Standard
in cooling & dry
ࠞ
: Drain pump is run during cooling and dry.
ࠝ
Operate in standard & heating
ࠞ
: Drain pump is run during cooling, dry and heating.
ࠝ
Operate in heating & fan
ࠞ
: Drain pump is run during cooling, dry, heating and fan.
ࠝ
Operate in standard & fan
ࠞ
: Drain pump is run during cooling, dry and fan.
(ii)
(iii)
(iv)
Note (1) Values in
〔
〕
are for the RC-EX3A model.