175
–
'18 • KX-SM-292
7. To remove the heat exchanger assembly
(1) Remove the drain pan.(See No.4)
(2) Remove 4 heat exchanger assy
fi
xing screws and remove it.( mark)
8. To remove the impeller and motor (FM)
(1) Remove control box.(See No.1)
(2) Disconnect the motor connector(CNM) on PCB in control box.
(3) Remove the heat exchanger assembly.(See No.7)
(4) Remove the impelle
r fi
xing nut and remove it.( mark)
(5) Remove 4 mot
or fi
xing bolts and remove it.( mark)
(6) Tak
e off
the hooks of cover and remove it.
9. To remove the sensors (example"Thi-R1")
(1) Remove control box.(See No.1)
(2) Disconnect the Tho-R1 connector(CNN) on PCB in control box.
(3) Pull out the temperature sensor "Thi-R1" from the sensor holder.
10. To remove the Electronic Expansion Valve (EEV)
(1) Remove the heat exchanger assembly.(See No.7)
(2) Remove the coil of EEV by pull out on the top.
(3) Remove welded part of EEV by welding.( mark)
PROCEDURE & PICTURES
UFM
DAM
Cover
EEV
Coil of EEV
General view
Summary of Contents for FDC224KXZME1
Page 169: ... 168 18 KX SM 292 PHA012D402 ...
Page 170: ... 169 18 KX SM 292 Screw ...
Page 171: ... 170 18 KX SM 292 ...
Page 172: ... 171 18 KX SM 292 ...