25
–
'18 • KX-SM-292
(A) Normal control
(1) Operation of major functional components under each operation mode
Operation mode
Functional item
Cooling/Dehumidifying
Fan
Heating
Thermostat
ON
Thermostat
OFF
Defrost
Thermostat
ON
Thermostat
OFF
Compressor (CM)
〇
×
×
〇
×
〇
Magnetic contactor CM1 (52X1, 52X2)
〇
〇
×/〇
〇
〇
〇
Outdoor fan mortor (FMo-1)
〇
×/〇
×/〇
〇/×
×/〇
〇→×
Outdoor fan mortor (FMo-2)
〇/×
×/〇
×/〇
〇/×
×/〇
〇→×
4-way valve (20S)
×
×
×
〇
〇
〇→×
Heating electronic expansion valve
(EEVH)
Fully open
Fully open
※
1
Opening Angle
Control
※
2
Fully closed /
Fully open
Super cooling coil electronic expansion
valve (EEVSC)
Opening Angle
Control
Fully closed Fully closed Fully closed Fully closed Fully closed
Solenoid valve (SV1) (oil return)
〇/×
×
×
〇/×
×
〇/×
Solenoid valve (SV6) (fluid return)
〇/×
〇/×
×
〇/×
〇/×
〇/×
Solenoid valve (SV11) (gas bypass)
×
×
×
〇/×
×
×
Crankcase heater (CH)
〇/×
〇/×
〇
〇/×
〇/×
〇/×
Notes (1) It means
〇
: ON,
×
: OFF,
〇/×
: -,
×/〇
: ON or OFF.
(2) This shows the state of output when all indoor units are under the same mode.
(3)
※
1 : When stopped from cooling, it is fully open
When stopped from heating, it is fully closed unless another degree of opening is specified by the electronic expansion valve (EEV) control
at the stop.
※
2 : When stopped from heating, it is fully closed unless another degree of opening is specified by the electronic expansion valve (EEV) control
at the stop.
1.4 Operation control function by the outdoor control