26
–
'18 • KX-SM-292
(2) Compressor pre-start control
(a) Remote control full stop
→
Operation
(i) Starting conditions
• When it has changed to the compressor operation frequency command > 0 Hz from the state of compressor stopping.
(ii) Control contents
• It sets the compressor operation frequency command = 0 Hz, and then after this control ends, It starts the
compressor.
(iii) Ending conditions
When all of following conditions are satisfied
①
It has elapsed 15 seconds after the start of this control.
• Meaning of marks
52X1, 52X2 Solenoid for compressor
CM
Compressor
EEVH
Heating electronic expansion valve
EEVSC
Subcooling coil electronic expansion valve
SV6
Solenoid valve [Oil return]
―
―――
ON
15 seconds
6 seconds
Normal control
Normal control
Initial opening
Initial opening
3 minutes
Time
2 minutes
Stop
OFF
0 rps
Opening at stop
0 pulse
OFF
Starting condition established
Operation
52X1, 52X2
CM
EEVH
EEVSC
SV6
ON