30
–
'18 • KX-SM-292
< Ending conditions >
When either one of following conditions is established
a) When the frequency upper limit increase by this control continued for 15 minutes in total
When the inverter has stopped within 15 minutes after the start and is started again, it starts with the normal
protection start and increases the frequency upper limit at a rate of 5 rps/minute till the frequency increase
continues for 15 minutes in total.
(iii) Compressor protection start B
< Control contents >
➀
Compressor maintains operation at lower limit frequency, after 4-way valve switching safeguard ends.
If the time from starting till reaching the lower limit frequency after 4-way valve switching safeguard operation
has elapsed 2 minutes, the target frequency is changed to that of 2 minutes later from the lower limit frequency.
➁
For 18 minutes after starting, the target frequency is increased at a rate of 5 rps/2 minutes from the lower limit
frequency.
➂
For 18 minutes after starting, the starting point of this control is the completion point of inverter start (10 rps).
➃
From 18 minutes to 24 minutes, it is increased at a rate of 5 rps/minute.
< Ending conditions >
When either one of the following conditions is established
a) This frequency-up control will end when the cumulative operation time after starting becomes 24 minutes.
If the inverter stopped within 24 minutes after starting and starts again, it starts with Compressor protection
start, normal and increases the frequency at a rate of 5 rps/minute till the cumulative operation time after
starting becomes 24 minutes.
However, if 45 minutes have been elapsed since inverter stopped and starts again, it starts with Compressor
protection start A
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
120
100
80
60
40
20
Compressor inverter frequency (rps)
Upper limit frequency
Speed control
Lower limit frequency
Time (minute)
Start
0
2
4
6
8
10
12
14
16
18
20
22
24
120
100
80
60
40
20
Compressor inverter frequency (rps)
Time (minute)
Start
Speed control
Upper limit frequency
Lower limit frequency