31
–
'18 • KX-SM-292
< Ending conditions >
When either one of following conditions is established
a) When the frequency upper limit increase by this control continued for 15 minutes in total
When the inverter has stopped within 15 minutes after the start and is started again, it starts with the normal
protection start and increases the frequency upper limit at a rate of 5 rps/minute till the frequency increase
continues for 15 minutes in total.
(iii) Compressor protection start B
< Control contents >
➀
Compressor maintains operation at lower limit frequency, after 4-way valve switching safeguard ends.
If the time from starting till reaching the lower limit frequency after 4-way valve switching safeguard operation
has elapsed 2 minutes, the target frequency is changed to that of 2 minutes later from the lower limit frequency.
➁
For 18 minutes after starting, the target frequency is increased at a rate of 5 rps/2 minutes from the lower limit
frequency.
➂
For 18 minutes after starting, the starting point of this control is the completion point of inverter start (10 rps).
➃
From 18 minutes to 24 minutes, it is increased at a rate of 5 rps/minute.
< Ending conditions >
When either one of the following conditions is established
a) This frequency-up control will end when the cumulative operation time after starting becomes 24 minutes.
If the inverter stopped within 24 minutes after starting and starts again, it starts with Compressor protection
start, normal and increases the frequency at a rate of 5 rps/minute till the cumulative operation time after
starting becomes 24 minutes.
However, if 45 minutes have been elapsed since inverter stopped and starts again, it starts with Compressor
protection start A
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
120
100
80
60
40
20
Compressor inverter frequency (rps)
Upper limit frequency
Speed control
Lower limit frequency
Time (minute)
Start
0
2
4
6
8
10
12
14
16
18
20
22
24
120
100
80
60
40
20
Compressor inverter frequency (rps)
Time (minute)
Start
Speed control
Upper limit frequency
Lower limit frequency
(4) Outdoor fan control
(a) Outdoor fan speed and fan motor rotation speed.
The 7th outdoor fan speed in the following table is specified as the rated speed. Under the normal control, the speeds up
to 8th level (800 min
-1
) are used.
Note (1) Figures in the parentheses in the above table are applicable to FDC224KXZME1.
(b) Fan control during cooling
During cooling and dehumidifying, fan speed is controlled in accordance with the high pressure (sensed by PSH) and the
outdoor air temperature (sensed by Tho-A).
(i) Initial fan speeds are as follows.
Initial ourdoor fan speed at cooling
(ii) During normal operation, the speed is changed in accordance with the high pressure value.
➀
When it has detected HP
≧
2.2 MPa for 1 minute continuously, the fan speed is raised by one tap.
➁
When it is 1.5 MPa < HP < 2.2 MPa, the present fan speed is maintained.
➂
When it has detected HP
≦
1.5 MPa for 1 minute continuously, the fan speed is dropped by one tap.
➃
Control range of fan speed is 1th – 8th speeds.
(iii) When states under this control change from HP < 3.3 MPa to HP
≧
3.3 MPa, the fan speed is changed preferentially
to the followings. (After the change it returns to the normal control.)
➀
When the outdoor air temperature
≧
30ºC, it changes to 7th or higher speed.
➁
When the outdoor air temperature < 30ºC, it changes to 3th or higher speed.
➂
When the fan speed was higher than the above before the change of states, the fan speed is not changed.
Outdoor fan tap
Cooling
Heating
FMo1 [min
-1
]
FMo2 [min
-1
]
FMo1 [min
-1
]
FMo2 [min
-1
]
0th speed
0
0
0
0
1st speed
200
0
200
0
2nd speed
200
200
200
200
3rd speed
300
300
300
300
4th speed
400
400
400
400
5th speed
500
500
500
500
6th speed
575
575
575
575
7th speed
740
740
740
740
8th speed
800
800
800 (780)
800 (780)
Model
Outdoor air temp. ≤ 10ºC
10ºC < Outdoor air temp. < 15ºC
15ºC ≤ Outdoor air
temp.
All models
2nd speed
4th speed
6th speed
1.5
2.2
One tap up
Maintained
One tap down
High pressure (MPa)