46
–
'18 • KX-SM-292
(11) VTCC : Variable Temperature and capacity control (VRF inverter Multi-system energy save control)
On the multi-system, target pressures are set uniformly so that indoor units operate with a constant capacity and repeat the
ON/OFF control with which thermostats are turned OFF when temperatures become near the setting temperature.
Owing to the tuning of target high/low pressure near the setting temperature, it becomes possible to perform the high effi-
ciency operation near the setting temperature.
For this reason, duration of time for highly efficient operation is increased by providing the compressor upper limit speed
according to the thermostat ON capacity.
・
Thermostat ON capacity … Total capacity of indoor units which are operating with the thermostat ON
(a) Correction of target high/low pressure
(i) Starting condition (either of
①
or
②
)
①
When the external input function assignment [P07] - [P10]: Multi-system energy save control = Valid
②
When 7-segment [P39] (Multi-system energy save control I) = ON, if the external input function assignment [P07]
- [P10] is not assigned this control.
(ii) Contents of control
①
During the outdoor unit operation mode at cooling
・
Indoor load more than 50% → Corrected to the target cooling low pressure lower.
・
Indoor load less than 50% → Corrected to the target cooling low pressure higher.
②
During the outdoor unit operation mode at heating
・
Indoor load more than 50% → Corrected to the target heating high pressure higher.
・
Indoor load less than 50% → Corrected to the target heating high pressure lower.
(Total capacity of indoor units of which load is high)
(Note) Indoor load condition (%) =
――――――――――――――――――――――
Total capacity of indoor units with the thermostat ON
(iii) Ending condition
①
When the starting conditions are lost.
●
Pump down by external input
Emergency call => External operation input : Shorted
Alarm unit
Gas leakage
Pump down
operation
Activate by 7-segment:[P77]=“1”
E63
<==