47
–
'18 • KX-SM-292
(b) Compressor upper limit speed restriction for each operation capacity
(i) Starting condition (either of
①
or
②
)
①
When the external input assignment [P07] – [P10]: Multi-system energy save operation = Valid and 7-segment [P67]
(Multi-system energy save control II) = 1 or 2 or 3
Factory default: 0 (OFF)/1 (Setting 1), 2 (Setting 2), 3 (Setting 3)
②
7-segment [P67] = 1 or 2 or 3, if the external input function assignment [P07] – [P10] is not assigned this control.
(ii) Contents of control
①
Compressor upper limit speed is the value obtained by multiplying with the upper limit speed restriction rate ac-
cording to the thermostat ON capacity.
②
The upper limit restriction rate is divided to the following 3 steps according to each setting of [P67] as follows.
Upper limit speed restriction rate
Upper limit Fk
(Normal)
Setting 1: 60%
Thermostat ON capacity
Setting 2:40%
Setting 3:20%
0
100%
③
Following controls supersede this control.
・
4-way valve safeguard
・
Defrost operation
・
Oil return operation
・
Oil equalized operation
・
Pump-down operation for replacement
・
Start/Stop pump-down operation
(iii) Ending condition
①
When the starting conditions are lost.