54
–
'18 • KX-SM-292
Code
No.
Data display contents
Data display range
Min.
unit
Remarks
<Service engineer setting>
P16 (Spare)
– –
– –
– –
–
P17 (Spare)
– –
– –
– –
–
P18 (Spare)
– –
– –
– –
–
P19
Preferencial switch to ensure
certain indoor outlet air
temperature at heating
0 : (Factory default)
0.1
–
0: Control for ensuring certain indoor outlet air temperature
at heating is valid
1: Control for ensuring certain indoor outlet air temperature
at heating is invalid
P20
Allowable total capacity of
thermostat ON indoor units
to ensure certain indoor outlet
temperature at heating
110 : (Factory default)
100, 090, 080
Changes to 110, 100, 090, 080, 110 …
P21
Allowable number of
thermostat ON indoor units
to ensure certain indoor outlet
temperature at heating
0 : (Factory default)
0 - 9
1
10
P22 (Spare)
– – – –
– –
–
P23 (Spare)
– – – –
– –
–
P24 (Spare)
– – – –
– –
–
P25 (Spare)
– – – –
– –
–
<New Superlink setting>
P30
Superlink communication
status
0,1
–
0: Previous Superlink
1: New Superlink
P31
Automatic address setting
start input
0 : (Factory default)
0,1
–
0: Automatic address setting standby
1: Automatic address setting start
P32
Input the starting indoor
address for automatic address
setting
1 : (Factory default)
1 - 127
1
Specify the starting indoor address connected in one
refrigerant system for automatic address setting.
P33
Input the number of connected
indoor units
1 : (Factory default)
1 - 24 (*)
1
Specify the number of indoor units connected in one
refrigerant system for automatic address setting.
(*) Maximum connectable number of indoor units for
each outdoor unit
P34 Polarity difinition
0 : (Factory default)
0,1
–
0: Network polarity not defined
1: Network polarity defined
P36 (Spare)
–
P37 (Spare)
–
P38 (Spare)
P39 Multi
・
system energy save control
Ⅰ