71
–
'18 • KX-SM-292
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
None
Excessive noise/vibration (3/3)
–
–
–
–
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
[Adjustment
during commissioning]
Does noise/vibration occur when the
cooling/heating operation is
performed under anomalous
condition?
From 2/3
YES
If insufficient cooling
heating problem happens
due to anomalous operating
conditions at cooling
/heating, followings are
suspicious.
• Excessive charged
amount of refrigerant
• Insufficient charge
amount of refrigerant
• Intrusion of air, nitrogen,
etc.
In such case, it is necessary
to recover refrigerant,
vacuum-dry and recharge
refrigerant.
* Since there could be
many causes of noise/
vibration, the above may
not cover all.
In such case, check the
conditions when, where,
how the noise/vibration
occurs according to
following check points and
ask our consultation.
• Indoor/outdoor unit
• Cooling/heating/fan
mode
• Startup/stop/during
operation
• Operating condition
(Indoor/outdoor
temperatures and
pressures)
• Time it occurred
• Operation data retained
by remote control
or Mente PC such as
compressor rotation
speed, heat exchanger
temperature, EEV
opening degree and etc.
• Tone (If available, record
the noise)
• Any other anomalies
2. Error detection method
3. Condition of error displayed
4. Presumable cause
Note:
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
None
Louver motor anomaly
Keeps flashing Stays Off
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
Is LM harness
broken?
Is there
any disconnection
or breakage of LM
connector?
Is LM locked?
Does LM turn
smoothly?
Is there
any problem on
the connection
link?
˜Check at the indoor unit side.
Is the
setting of air flow
direction change
prohibited?
Check how LS reacts
when the power is turned
OFF and ON again
Check the remote control whether
it is fixed free flow setting.
YES
Does the louver
link press LS till crick sound
can be heard?
NO
NO
YES
In cases of FDTW, FDTS and FDTQ
Does the
louver operate when
power on?
Notes (1) LM: Louver motor
(2) LS: Limit switch
YES
NO
NO
NO
NO
YES
Operate after waiting for more than 1 minute.
It is normal if LM can
be stopped by pressing
LS two times.
In cases of FDT, FDTC, FDE and FDK
Check the remote control whether
it is fixed free flow setting or not.
Correct it.
Repair harness.
Check connector (CnJ).
Replace Louver Motor.
Correct it.
Correct it.
Replace indoor unit control
PCB.
Correct it.
Adjust LM lever and then
check again.
• LS anomaly
Replace.
• Indoor unit control PCB
anomaly
Replace.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Louver motor anomaly
• Disconnection/breakage of
LM harness
• Limit switch anomaly
Note:
NO
NO
NO
YES
YES
Summary of Contents for FDC224KXZME1