78
–
'18 • KX-SM-292
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
WAIT
WAIT
(5)
Stays OFF Stays Off
Stays OFF Stays Off
1. Applicable model
5. Troubleshooting
All models
(In case that LED on outdoor
unit control PCB stays OFF)
Diagnosis
Countermeasure
In case that LED on
outdoor unit control PCB stays
OFF
Is
power fuse (5A) on the
outdoor unit conrol PCB
blown?
Is
AC380-415V detected at
secondary side of noise
filter?
Are
connecting wires between
noise filter and inverter PCB
connected properly?
Is
the connection of
connecting wire of reactor
OK?
Is
there any anomaly on
outdoor fan motor?
Once turn OFF the breaker
and turn ON it again at 3
minute after power OFF
Does it become normal?
Check inverter before
replacement of 52C
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
A
B
Normal
(Malfunction by temporary
noise)
Refer next page
Replace noise filter.
Connect the connecting
wire properly.
Correct connection.
(In case of breakage of
wire replace it)
Outdoor unit control PCB
anomaly
Replace it.
Outdoor unit fan motor
anomaly
Replace it.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Fuse blown
• Noise filter anomaly
• Anomalous connection of
wire between PCBs
• Indoor unit control PCB anomaly
• Remote control anomaly
• Breakage of connecting wires
of remote control
• Outdoor unit control PCB anomaly
Note: