'18 • KX-SM-292
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E5
-
Communication error during operation
Keeps flashing *See below
Keeps flashing 2 time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Does
the remote control LCD
becomes normal?
Reset the power source and restart.
YES
NO
* In case that indoor unit red LED stays OFF
Is the
connection of signal wires
at the outdoor unit side
OK?
Is the
connection of signal wires
(between indoor and outdoor units)
OK?
Does the
remote control LCD
becomes normal?
Note (1) Check the connection (disconnection, looseness)
of signal wires at outdoor unit terminal block
Reset the power source and restart.
Note (2) Check the connection (disconnection, looseness,
brakage) of signal wires (between indoor and
outdoor units)
YES
NO
YES
NO
YES
NO
* In case that indoor unit red LED flashes 2 times
Repair signal wires.
Repair signal wires.
Go to the diagnosis of
WAIT
(1).
Unit is normal.
(Malfunction by temporary
noise, etc.)
Outdoor unit control PCB anomaly
(Network communicaion
circuit anomaly)
→
Replace it.
Unit is normal.
(Malfunction by temporary
noise, etc.)
2. Error detection method
When the communication
between indoor and outdoor
units is interupted for more than
2 minutes
3. Condition of error displayed
When this anomaly is detected
during operation.
4. Presumable cause
• Unit address No. setting error
• Remote control wires broken
• Poor connection/disconnection
of remote control wires
• Indoor unit control PCB anomaly
Note:
When the pump down switch is turned on, communication between indoor and outdoor units is cancelled so that
"Communication error E5" will be displayed on the remote control and indoor unit control PCB, but this is normal.
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E6
-
Indoor unit heat exchanger
temperature sensor anomaly (Thi-R)
Keeps flashing 1 time flash
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is
the connector of
sensor connected
properly ?
Regarding the characteristics of
the sensor, see the following chart
Are
the characteristics
of sensor OK?
*1
NO
NO
YES
*1 Check several times to prove any poor connection
YES
T
empearture sensor resistance (kΩ
)
Temperature-resistance characreristics of indoor unit heat
exchanger temperature sensor (Thi-R1, R2, R3)
5kΩ at 25ºC
T
emperature (ºC)
Insert the connector
securely.
Replace sensor (Thi-R).
Replace indoor unit control
PCB.
2. Error detection method
Detection of anomalously low
temperature (resistance)
of Thi-R1, R2, R3
3. Condition of error displayed
•
If -50ºC or lower is
detected for 5 seconds
continuously, compressor
stops. After 3 minutes delay,
the compressor is restarted
automatically, but if this
anomaly occurs again within
60 minutes after the initial
detection.
•
Or if 70ºC or higher is
detected for 5 seconds
continuously.
4. Presumable cause
• Anomalous connecion
of indoor unit heat exchanger
temperature sensor
• Indoor unit heat exchanger
temperature sensor
anomaly
• Indoor unit control PCB anomaly
Note: