–
96
–
'18 • KX-SM-292
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E32
E32
Open L3 Phase on
power source at primary side
Keeps flashing Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
Is the power
source voltage (between phases) at
the primary side OK?
Save data for 30 minutes before
stopping in Mente PC
Does E32 recur?
YES
Reset the power source
and restart operation.
NO
YES
NO
Check and save the data of
operating condition.
Check the conditions
whether it occurs
immediately after the
power on or during
operation or stopping.
(It will be useful to
persuade the customer why
an improvement of power
source is required by
showing these data.)
Propose an improvement to
the customer.
Check it, as much as
possible, under the
operating conditions for
30 minutes before error
occurred.
Replace outdoor unit control
PCB.
Wait and see without taking
any action.
2. Error detection method
By Checking the power source
voltage at primary side of the
outdoor unit control PCB
(Check only L3 phase)
3. Condition of error displayed
When the power source voltage
between L1-L3 or L2-L3
becomes 0V and/or the current
of L3 decrease to 0A
4. Presumable cause
• Anomalous power source at
primary side
• Outdoor unit control PCB
anomaly.
Note:
Summary of Contents for FDC224KXZME1
Page 169: ... 168 18 KX SM 292 PHA012D402 ...
Page 170: ... 169 18 KX SM 292 Screw ...
Page 171: ... 170 18 KX SM 292 ...
Page 172: ... 171 18 KX SM 292 ...