Error code
Remote control:
7-segment display: –
LED
Green
Red
Indoor
Outdoor
Content
'14 • KX-SM-221
E40
E40
High pressure anomaly
(63H1 activated)
Keeps flashing
Stays OFF
Keeps flashing 1-time flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
YES
YES
NO
Save data for 30 minutes before stopping in Mente PC.
Connect a pressure gauge and
restart operation.
YES
YES
NO
Was 63H1
activated at 4.15MPa
or higher?
Does the sensed
value of the high pressure
sensor show 4.15MPa?
(Normal?)
Are the
63H1 OK?
Are the connector and/or
harness
OK?
NO
Are the
service valves fully
open?
YES
Is it
stop at 4.15MPa of gauge
pressure ?
Is there any
clogging in the refrigerant
circuit ?
NO
NO
NO
YES
Check and save the data of
operating condition.
Check the sensed value of
high pressure sensor when the
63H1 is activated.
Check whether the high
pressure switch is activated
at the sensed value of high
pressure sensor.
High pressure sensor
anomaly is suspicious.
Check high pressure sensor
itself according to the
troubleshooting procedure of
E54, after restarting operation.
(If the high pressure sensor
[PSH] fails, replace it)
If the connector is
disconnected or the harness
is broken, correct it.
Also check whether the
high pressure switch is
properly mounted or not.
Check the open N phase on
power source
Open operation valve.
Check it, as much as
possible, under the
operating conditions for
30 minutes before error
occurred.
Replace outdoor control
PCB.
Remove clogs.
Check items (condenser
side):
• Filter clogging
• Airflow volume (Fan
motor)
• Short-circuit of airflow
2. Error detection method
When high pressure switch
63H1 is activated.
3. Condition of error displayed
• If high pressure exceeds
4.15MPa
• If 63H1 is activated 5 times
within 60 minutes
• If 63H1 is activated for 60
minutes continuously
4. Presumable cause
• Short-circuit of airflow
at condenser side of heat
exchanger/Disturbance of
airflow/Clogging filter/Fan
motor anomaly
• Disconnection of high
pressure switch connector
• Breakage of high pressure
switch harness
• Closed service valves
• High pressure sensor anomaly
• High pressure switch anomaly
Note:
If the error does not recur, connect the Mente PC and continue to collect data.
E40
-
100
-