Error code
Remote control:
7-segment display: –
LED
Green
Red
Indoor
Outdoor
Content
'14 • KX-SM-221
E48
E48
Outdoor DC fan motor anomaly(2/2)
Keeps flashing
Stays OFF
Keeps flashing
*1
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
2. Error detection method
• If 400 min
-1
or lower of the
fan rotation command and the
state of overcurent are detected
for 10 times continuously.
(CNFAN terminal:
Between 5-2 pins …
Hi output
⇒
Overcurrent
Lo output
⇒
Normal)
• If 100 min
-1
of the actual fan
rotation speed is detected for
30 seconds.
3. Condition of error displayed
Speed of 400 min
-1
or less
is commanded, and state of
overcurrent is communicated.
4. Presumable cause
• Broken or disconnected wire
• Faulty fan motor
• Defective inverter PCB
• Defective control PCB
• Defective power transistor
• Defective diode module
• Defective surge suppressor
resistor
Note:
*1 1-time flash : FMo1, 2-time flash : FMo2
Power OFF
From previous page
Does speed command voltage of
control PCB rise gradually and stabilize
after a rise of several V?
Is power transistor or diode
module short-circuited?
Is surge suppressor resistor
coil blown on any line?
Replace control PCB.
Replace surge suppressor resistor
on the line. (Disconnect harness
from resistor, and measure resistance
between terminals.
Replace power transistor or diode
module on poorly insulated line.
(For check method of short-circuit,
see page 58.)
Replace No. 1 or 2 fan motor.
※
3
NO
NO
NO
YES
YES
YES
E48
-
108
-