Error code
Remote control:
7-segment display: –
LED
Green
Red
Indoor
Outdoor
Content
'14 • KX-SM-221
E58
E58
Anomalous compressor
by loss of synchronism
Keeps flashing
Stays OFF
Keeps flashing 1-time flash
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
2. Error detection method
E58 is displayed on 7-segment
LED.
3. Condition of error displayed
This anomaly is established 4
times within 15 minutes.
4. Presumable cause
• Insufficient time elapsed after
the power supplied, before
compressor startup.
(Startup the compressor
wihtout crankcase heater ON)
• Compressor anomaly
• Inverter PCB anomaly
• Power transitor anomaly
Note:
*1 Measurement position: B and - of C19
*2 Measurement position: Check resistance between P-U, P-V, P-W, N-U, N-V, N-W, P-N. (Disconnect wires from compressor beforehand.)
If it fails to repeat, connect the Mente PC, and continue to collect data.
Is there
inverter output?
(
*
1)
Save data for 30 minutes before stopping in Mente PC.
YES
YES
YES
(Repeats on two units.)
YES
(Repeats on one unit only.)
NO
(Not repeat on both units.)
Evaluate data 30 minutes earlier.
Turn power ON (after 1 hour if possible), and operate again.
Change wire connections
on inverter and compressor,
and operate again.
Is it initial startup within 1
hour after power ON?
Is there record of
replacement of inverter PCB?
Is DC 15 V
detected on inverter
PCB?
Check inverter PCB for
defect with the checker.
Other
(Including checker
not available
Power
transistor
error
Short-
circuited.
Good
Check resistance between
power transistor modules.
(Is it short-circuited?)
(
*
2)
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
Is there poor connection on wires
to compressor terminals?
Does the system have
one compressor only?
Does it repeat?
Does it repeat?
Check, record operating condition.
Coolant may be stagnated. Wait for approx.
1 hour after power ON before restarting
operation. (Supply power to crankcase
to evaporate liquid coolant in compressor.)
Model setting may be wrong.
Check setting of dip switches.
Replace wires.
(If terminal block at compressor
side is faulty, replace compressor.)
Wait and see.
Replace compressor.
Measure after confirming that
52X is turned ON.
Replace power transistor.
Replace power transistor.
Replace inverter PCB.
Replace compressor.
Wait and see.
Does it repeat on
other compressor?
NO
E58
-
112
-