126
–
'14 • KX-SM-221
-
9
-
'14 • KX-DB-220D
4. PIPING SYSTEM
Models FDC224KXZPE1, 280KXZPE1
Notes (1) Preset point of protective device
63H1 : Open 4.15MPa, Close 3.15MPa
(For protection)
(2) Function of thermistor
PSH : For compressor control
3.70 ON (MPa)
PSL : ON 0.18MPa, OFF 0.20MPa
(For compressor control)
ON 0.134MPa, OFF 0.18MPa
(For protection)
Thi-R1, R2 : Heating operation : Indoor fan control.
Cooling operation : Frost prevention control.
Super heat control.
Thi-R3 : For super heat control of cooling operation.
Tho-D1 : For control of discharge pipe temperature.
Tho-C1 : For control of temperature under the dome.
Tho-S : For control of suction pipe temperature, super heat control.
Tho-R1: For control of defrosting.
Tho-A : For control of defrosting.
Tho-SC :
Electronic expansion valve (EEVSC) control of cooling operation.
Tho-H : For super heat control of sub-cooling coil.
Gas line
Liquid line
Strainer
Electronic
expansion valve
Strainer
To next indoor units
(Thi-R2)
Thermistor (Entrance)
(Thi-A)
Thermistor
Thermistor (Exit)
(Thi-R3)
Thermistor (Bend)
(Thi-R1)
(Thi-R2)
Thermistor
(Thi-A)
Thermistor (Entrance)
(Thi-R3)
Heat
exchanger
Outdoor unit
Indoor unit
Electronic
expansion valve
(EEVSC)
High pressure
sensor (PSH)
4way valve (20S)
Sub-cooling coil
Thermistor
(Tho-SC)
(Tho-C1)
Thermistor
Compressor
CM1
Oil
separator
Check valve
Thermistor
(Tho-D1)
Service valve
Receiver
(Tho-A)
Sub-cooling coil
Thermistor
(Tho-S)
(
Tho-R
1)
Thermisto
r (Exit)
Thermistor
Muffler
Capillary tube
Heat
exchanger
Strainer
Electronic
expansion valve
Strainer
Indoor unit
Thermisteor (Bend)
(Thi-R1)
Strainer
Solenoid valv
e(
SV
6)
Capillary tube
Service valve
Strainer
Strainer
Strainer
High pressure
switch(63H1)
Strainer
Solenoid valve
(
SV
1)
Capillary tube
Accumulator
Low pressure
sensor (PSL)
Check joint
Sub-cooling coil Thermistor (Tho-
H)
Sub-cooling coil
Strainer
Electronic expansion valve (EEVH
2)
Heat
exchanger
Thermistor (Exit)
Capillary tube
Receiver