'14 • KX-SM-221
1.4 Operation control function by the outdoor control
(A) Normal control
(1) Operation of major functional components under each operation mode
-
9
-
'14 • KX-SM-221
1.4 Operation control function by the outdoor control
(A) Normal control
(1) Operation of major functional components under each operation mode
Operation mode
Fonctional compornents
Cooling/Dehumidifying
Fan
Heating
Thermostat
ON
Thermostat
OFF
Defrost
Thermostat
ON
Thermostat
OFF
Compressor [CM]
〇
×
×
〇
×
〇
Magnetic contactor CM1 [52X1, 52X2]
〇
〇
〇/×
〇
〇
〇
Outdoor unit fan mortor [FMo-1]
〇
〇/×
〇/×
〇/×
〇/×
〇→×
Outdoor unit fan mortor [FMo-2]
〇/×
〇/×
〇/×
〇/×
〇/×
〇→×
4 way valve (20S)
×
×
×
〇
〇
〇→×
Electronic expansion valve for
heating [EEVH]
Fully open
〇/×
※
1
Opening Angle
Control
※
2
Fully closed /
Fully open
Electronic expansion valve for
sub-cooling coil [EEVSC]
Opening Angle
Control
Fully closed
Fully closed
※
2
Fully closed
Fully closed
Solenoid valve [SV1] (liquid injection
〇/×
×
×
〇/×
×
〇/×
Solenoid valve [SV6] (oil return)
return)
〇/×
〇/×
×
〇/×
〇/×
〇/×
Crankcase heater [CH]
〇/×
〇/×
〇/×
〇/×
〇/×
〇/×
Note (1) It means
〇
: ON,
×
: OFF,
〇/×
: ON or OFF,
〇→×
: ON
→
OFF
(2) This shows the state of output when all indoor units are under the same mode.
(3)
※
1 : When stopped from cooling, it is fully open
When stopped from heating, it is fully closed unless another degree of opening is specified by the electronic expansion valve (EEV) control at
the stop.
※
2 : When stopped from heating, it is fully closed unless another degree of opening is specified by the electronic expansion valve (EEV) control at
the stop.
T
ESP-FP-2091
Indoor unit fan
Indoor unit electronic expansion
valve
Remote control
command
Superheating
control response
Outlet temperature
control response
Fully closed
Fully closed
Slight opening
control
Model-specific
aperture opening
angle
Depend on remote
control setting
Remote control
command
Remote control
command
Depend on remote
control setting
〇→×
T
ESP-FP-2091