'14 • KX-SM-221
(B)
Optional controls
• Functions of outdoor PCB connector CNS1 and CNZ1
➀
CNS1 connector : By changing the allocation of external input functions [P07-"X"] on the 7-segment, following
functions can be selected.
➁
CNZ1 connector : By changing the allocation of external input functions [P06-"X"] on the 7-segment, following
functions can be selecte.
(1) External input and demand input
(a) Operation permission and prohibition modes
(Note) With -segment display [P0]-[0]
(i) Operation permission or operation prohibition mode is switched with the connector (CnS) and the jumper wire (J)
on the outdoor PCB.
J: Switching of CnS input method
J short-circuited: CNS is for the level input.
J open: CnS is for the pulse input.
(ii) Operation permission/prohibition control by the external input CnS of outdoor unit
Input: CnS
Switching with J
CnS: Switching of operation permission/
prohibition modes
Short-circuit
Open
Short-circuit (Level input)
Operation prohibition mode
Operation permission mode
Open (Pulse input)
Switching of operation permission/
operation prohibition modes (Reversal)
Open
Short-circuit
Short-circuit (Level input)
Operation permission mode
Operation prohibition mode
Open (Pulse input)
(NOP)
Note () Factory setting – J: Short-circuit, CnS: Short-circuit (Short-circuit pin connected)
(iii) The operation condition is desplayed on the LCD of remote control and is transfered to optional centralised control.
Function No. "X"
CNS short circuited
CNS open
“0” : Extemal operation input
Operation permission
Operation prohibition
“” : Demand input
Invalid
Valid
“” : Forced cooling/heating input
Heating
Cooling
“” : Silent mode input
Valid
Invalid
“” :
Spare
“” : Outdoor fan snow guard control input
Valid
Invalid
“” : Test run extemal input
Test run start
Normail operation
“” : Test run extemal input
Cooling test run
Heating test run
“” : Silent mode input
Valid
Invalid
“” : Spare
“0” : AF periodic inspection display
Valid
Invalid
“” : AF error display
Valid
Invalid
“” : Building multi energy save control
Valid
Invalid
“0” : Operation output
“” : Error output
“” : Compressor ON output
“” : Fan ON output
“” : Oil return operation or defrost operation output
“” : High pressure control output to water spraying device, etc.
“ ~ ” : Spare