'14 • KX-SM-221
(6) Forced cooling/heating operation
(a) With this control, SW- on the outdoor PCB is turned ON and setting function [P0]-[] with -segment display so as to
forcibly determined whether the indoor unit is operated for cooling or heating.
(b) If any operation mode other than the forcible mode is commanded from indoor unit, the mode unmatch message is
displayed on the remote control or others and operation enters in the FAN mode.
SW-
CnS
Operation
ON
Open
Cooling only
Close
Heating only
OFF
Normal operation
(c) With the forced mode from indoor unit, if a different operation mode is commanded, following operations take place based
on the forced cooling/heating operation set with the -segment [P].
P=0: The operation mode unmatch is displayed on the remote control, etc., and it is changed to the fan
operation.
P=: It is operated with the forced cooling/heating operation mode.
Setting temperature for cooling...
℃
Setting temperature for heating...0
℃
(7) Emergency stop control
When one of indoor units receives the emergency stop signal through CnT terminal on the indoor control PCB from the device
like as refrigerant leakage detector and that information is transmitted to the outdoor unit, the outdoor unit stops operation and
emergency stop error message transmitted to all indoor units running.
It is able to make the emergency stop function effective by remote control indoor function setting.
(a) When the outdoor unit receives the “Emergency stop” command from the indoor unit, it makes all stop by error.
(b) And the “Emergency stop” command is transmitted to all indoor units and error code “E” is displayed.
(c) When the outdoor unit receives the “Emergency stop reset” command from the indoor unit, the “Emergency stop reset”
command is transmitted to all indoor units.