'14 • KX-SM-221
(8) Pump down operation control for removal of the unit
When an outdoor unit is discarded or removed, the pump down control is performed at the outdoor unit side in order to recover
the refrigerant quickly to the outdoor unit.
(a) Start conditions
This is implemented with the liquid service valve closed.
(i) Outdoor unit operation mode – Stop
(ii) Turn ON the test run cooling switch SW- (cooling).
(iii) Turn ON the pump down switch SW- (pump down).
(iv) Turn ON the test run switch SW5-1 when the above (i)-(iii) statuses are satisfied.
Note () Input before the power ON is invalid.
(b) Control contents
(i) Compressor starts under compressor start protection control and runs at target speed of pump down operation.
However, when the operation start conditions have been established during the -minute delay control of
compressor, the compressor starts after completing the -minute delay control.
Item
Model
Target compressor speed at pump down operation
FDCKXZPE
0rps
FDC0KXZPE
rps
(ii) As the start conditions are established, both red LED and green LED on the outdoor PCB flash continuously.
-segment display shows “PdS” (Channel 0) at the code display area.
(iii) During the pump down operation control, the protective controls (excluing low pressure protective control,
anomalous low pressure control and pressure ratio protection control) and the error detection control are effective.
(iv) The sub-cooling coil expansion valve (EEVSC) closes fully during the pump down control.
(c) End conditions
If any of the following conditions is satisfied, this control ends.
(i) If a low pressure (LP) ≤ 0.01MPa is detected for 5 seconds continuously, it ends normally and initiates the
followings.
➀
Red LED: keeps lighting
➁
Green LED: keeps flashing
➂
-segment display: PdE
➃
Remote control: Stop
(ii) Anomalous all stop by the error detection control
(iii) If the cumulative compressor operation time under the pump down control totals minutes (ending by time count
up), it stops and initiates the following.
➀
Red LED: stays OFF
➁
Green LED: keeps flashing
➂
-segment display: No display
➃
Remote control: Stop
(iv) When any of setting switches (SW-, SW- and SW-) has been turned OFF during pump down.
(Note) Even if only the pump down switch SW- is turned OFF, it does not recognized as the cooling test run mode , but stops.