'14 • KX-SM-221
-
2
-
When Special
display occurs
When Special
display reset
Special display
[CXX]
Button operation
No operation for 10 seconds*
* If the special display is reset in the meanwhile, it remains [CXX].
.;60
,QGLYLGXDOGH¿QLWLRQRIGLVSOD\FRQWHQWV!
[C49]
Sub-cooling degree at cooling mode
= High pressure saturated temperature (
°C
) detected with high pressure sensor (PHS)
- Sub-cooling coil temperature (
°C
) detected with sub-cooling temperature thermistor (Tho-SC)
During heating mode this data might be unreliable as sub-cooling degree, but the result is displayed as it is.
[C50]
Suction superheat degree
= Suction pipe temperature (
°C
) detected with suction pipe temperature thermistor (Tho-S)
- Low pressure saturated temperature (
°C
) detected with low pressure sensor (PLS)
[C51]
Superheat degree of sub-cooling coil
= Sub-cooling coil temperature (
°C
) detected with sub-cooling coil temperature thermistor (Tho-H)
- Low pressure saturated temperature (
°C
) detected with low pressure sensor (PLS)
[C52]
Superheat degree of under-dome
= Under-dome temperature (
°C
) detected with under-dome temperature thermistor (Tho-C)
- Low pressure saturated temperature (
°C
) detected with low pressure sensor (PLS)