'14 • KX-SM-221
-
4
-
Code
No.
Remarks
Contents of display
Data display
range
Minimum
unit
C40
C41
C42
C43
C44
C46
C47
C48
C49
C50
C51
C52
C54
C55
C56
C57
C66
C67
C68
0.00~2.00
1.60~4.15
0~999
0~130
1Hz
Cooling operation sub-cooling
Super heat
Super heat of sub-cooling coil
Tho-C1 Super heat
Target cooling low pressure
Target Fk
Inverter 1 operating frequency command
Minimum unit 1°C at -10°C or lower
Number of connected indoor unit
0~80
1
Capacity ratio of connected indoor unit
0~999
1
Number of operation indoor unit
0~50
Required Fk total
0~999
1Hz
Compressor cumulative operating time (CM1)
0~655
100h
Discharge pressure saturation temperature
-50~70
0.1°C
Suction pressure saturation temperature
-50~30
0.1°C
Minimum unit 1°C at -10°C or lower
Tho-SC1 saturated pressure
-0.68~4.15
0.01MPa
0~50
0.1deg
0~50
0.1deg
0~50
0.1deg
0.01MPa
Target heating high pressure
0.01MPa
1Hz
'14 • KX-SM-221
1%
0~50
0.1deg
< Information for outdoor unit >
< Control status >
C65
0~127
Outdoor unit operating mode pattern
(Spare)
1
0~127
Control status
1
0~127
Protection control status
1
See table on page 44
See table on page 44
0~127
Compressor stop causes
1
See table on page 45
C69
0~255
1h
Time elapsed after compressor stop cause
See page 39
See page 39
See page 39
See page 39
C59
C60
C61
0~999
0~999
0~100, Lo
10min
-1
FMo2 operating revolution command
Demand ratio
FMo1 operating revolution command
10min
-1
1%
Displays No. of the protection control of which effect is the strongest
among those occurred from the start of operation after the power on
Displays No. of the protection control of which effect is stronger thirdly
among those occurred from the start of operation after the power on
Displays No. of the protection control of which effect is stronger secondly
among those occurred from the start of operation after the power on
C70
C71
C72
0~127
0~127
1
Protection control causes 1
Protection control causes 2
1
Protection control causes 3
0~127
1