'14 • KX-SM-221
-
6
-
Code
No.
Remarks
Contents of display
Data display
range
Minimum
unit
P11
P12
P13
0: (Factory default)
0~9
110: (Factory default)
100,090,080
1
—
—
P30
P31
P32
P33
P34
0, 1
—
—
1
1
1
—
Superlink communication status
Start automatic address setting
Input starting indoor address
Input the number of connected indoor units
Polarity definition
P69
Multi-system energy save control I
< New Superlink setting >
0: Current Superlink
1: New Superlink
0: Automatic address setting standby
1: Automatic address setting start
0: Network polarity not defined
1: Network polarity defined
0: (Factory default)
0,
0: (Factory default)
0, 1
1
0: (Factory default)
1~127
24: (Factory default)
1~24(*)
Specify the starting indoor address connected in one refrigerant system
for automatic address setting.
Specify the number of indoor units connected in one refrigerant system
for automatic address setting.
(*) Maximum connectable number of indoor units for each outdoor unit
'14 • KX-SM-221
0, 1
0: (Factory default)
0: Heating air outlet temperature save control invalid (Factory default)
1: Heating air outlet temperature save control valid
Changes to 110,100,090,080, 110 .......
0: (Factory default)
0, 1
Switching to heating air outlet temperature save
priority
Capacity ratio of thermostat ON admission for
heating air outlet temperature save
Number of thermostat ON indemnification for
heating air outlet temperature save
1
CNS1 function assignment
0: External operation input
1: Demand input
2: Cooling/heating forced operation input
3: Silent mode input 1
P07
0: (Factory default)
0 ~ 20
4: —
6: Test run external input 1 (SW5-1 equivalent)
7: Test run external input 2 (SW5-2 equivalent)
8: Silent mode input 2
10: AF periodic inspection display
11: AF error display
12: Building multi energy save control
9, 13~20:Spare
5: Outdoor fan snow protection control input
P16
P17
P18
0, 1, 2, 3
0: (Factory default)
Multi-system energy save control II
1
1
1
0, 1
0: (Factory default)
After changing mode from operation prohibition
0, 1
0: (Factory default)
Mode unmatched indoor unit setting in forced
mode
mode
AUX
AUE
A01
A02
A03
A04
Auto address setting on
Indoor unit address No. assignment normal
ending
Indoor unit address No. assignment error 1
Indoor unit address No. assignment error 2
Indoor unit address No. assignment error 3
Superlink setting error