2.3 Contents of troubleshooting
(a) List of inspection displays
Indoor and outdoor units
Remote
control
error code
7-segment
display
Name of inspection
Classification
Page
E1
–
Remote control communication error
Communication error
78
E2
–
Duplicated indoor unit address
Address setting error
79
E3
–
Outdoor unit signal line error
Address pairing setting error
80
E5
–
Communication error during operation
Communication error
81
E6
–
Indoor heat exchanger temperature thermistor anomaly (ThI-R) Thermistor wire breakage
82
E7
–
Indoor return air temperature thermistor anomaly (ThI-A)
Thermistor wire breakage
83
E9
–
Drain trouble
System error
84
E10
–
Excessive number of indoor units (more than 17 units) by
controlling one remote control
Communication error
85
E11
–
Address setting error between master and slave indoor units Address setting error
86
E12
–
Address setting error by mixed setting method
Address setting error
87
E16
–
Indoor DC fan motor anomaly (FDT, FDTC, FDTW, FDTS,
FDU, FDUM, FDK, FDUT71, FDFW series)
DC fan motor error
88
E18
–
Address setting error of master and slave indoor units
Address setting error
89
E19
–
Indoor unit operation check drain motor check mode anomaly Setting error
90
E20
–
Indoor DC fan motor speed anomaly (FDT, FDTC, FDTW,
FDTS, FDU, FDUM, FDK, FDUT71, FDFW series)
DC fan motor error
91
E21
–
Detective panel switch operation (FDT)
Panel switch error
92
E28
–
Remote control temperature thermistor anomaly (Thc)
Thermistor wire breakage
93
E31
E31
Duplicated outdoor unit address No.
Address setting error
94
E32
E32
Open L3 Phase on power supply at primary side
Site setting error
95
E36
E36
Discharge pipe temperature error (Tho-D)
System error
96
E37
E37
Outdoor heat exchanger temperature thermistor (Tho-R)
and subcooling coil temperature thermistor (Tho-SC, -H)
anomaly
Thermistor wire
breakage
97
E38
E38
Outdoor air temperature thermistor anomaly (Tho-A)
Thermistor wire breakage
98
E39
E39
Discharge pipe temperature thermistor anomaly (Tho-D)
Thermistor wire breakage
99
E40
E40
High pressure anomaly (63H1 activated)
System error
100
E41(E51) E41(E51)-1,2 Power transistor overheat
System error
101
E42
E42
Current cut (CM1)
System error
102
E43
E43
Excessive number of indoor units connected, excessive total
capacity of connection
Site setting error
103
E44
E44
Liquid flooding anomaly (CM1)
System error
104
E45
E45
Communication error between inverter PCB and outdoor
control PCB
Communication error
105
E46
E46
Mixed address setting methods coexistent in same network
Address setting error
106
E48
E48
Outdoor DC fan motor anomaly
DC fan motor error
107, 108
E49
E49
Low pressure anomaly
System error
109
E53/E55
E53/E55
Suction pipe temperature thermistor anomaly (Tho-S),
Under-dome temperature thermistor anomaly (Tho-C1)
Thermistor wire
breakage
110
E54
E54
High pressure sensor anomaly (PSH)
Low pressure sensor anomaly (PSL)
Thermistor wire
breakage
111
E58
E58
Anomalous compressor by loss of synchronism
System error
112
E59
E59
Compressor startup failure (CM1)
System error
113
E63
E63
Emergency stop
Site setting error
114