Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
'14 • KX-SM-221
WAIT
WAIT
(5)
Stays OFF Stays OFF
Stays OFF Stays OFF
1. Applicable model
5. Troubleshooting
All models
(In case that LED on outdoor
control PCB stays OFF.)
Diagnosis
Countermeasure
In case that LED on
outdoor control PCB stays
OFF.
Is
power fuse (5A) on the
outdoor conrol PCB
blown?
Is
AC380-415V detected at
secondary side of noise
filter?
Are
connecting wires between
noise filter and inverter PCB
connected properly?
Is
the connection of
connecting wire of reactor
OK?
Is
there any anomaly on
outdoor fan motor?
Once turn OFF the breaker
and turn ON it again at 3
minutes after power OFF.
Does it become normal?
Check inverter before
replacement of 52C.
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
A
B
Refer next page.
From previous page.
Normal
(Malfunction by temporary
noise.)
Replace noise filter.
Connect the connecting
wire properly.
Correct connection.
(In case of breakage of
wire replace it.)
Outdoor control PCB
anomaly
Replace it.
Outdoor fan motor
anomaly
Replace it.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Fuse blown
• Noise filter anomaly
• Anomalous connection of
wire between PCBs
• Indoor control PCB anomaly
• Remote control anomaly
• Breakage of connecting wires
of remote control
• Outdoor control PCB anomaly
Note:
-
75
-