'09•KX-T-139
4
RANGE OF USAGE & LIMITATIONS
• Single use (also for combined use)
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
First branch
50~100m
MAX.
90m
MAX. 90m
MAX. 90m
MAX. 18m
MAX.
130m
50~100m
MAX.
130m
MAX. 18m
MAX. 18m
MAX. 18m
MAX. 18m
MAX. 18m
(Lowest indoor unit)
(Highest indoor unit)
(Highest indoor unit)
(Lowest indoor unit)
First branch
(Header)
denotes
System
FDCH450CKXE6G
FDCH504CKXE6G
Refer to page 15
1 to 40 unit
1 to 36 unit
1 to 36 unit
Item
Indoor air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Single direction piping length
Actual length : 160m or less, Eguivalent length : 185m or less
Total piping length
(2)
Main pipe length
1000m or less
130m or less
90m or less (However, difference between the longest and shortest piping : 40m or less)
6 min or more (3 minutes or more from start to stop or 3 minutes or more from stop to start)
3 min or more
Within 10% of rated voltage
50 ~100m
(3)
Prohibited activity
18m or less
Allowable pipe length from the first branching
18m or less
Elevation difference between the first branching point and the indoor unit
Number of connected units
Connectable capacity
(1)
FDCH400CKXE6G
200 ~ 800
225 ~ 900
252 ~ 806
Outdoor unit is higher
Outdoor unit is lower
Indoor units
that can be
used in
combination
Difference in
height between
indoor and outdoor
units
Difference in the elevation of indoor units in a system
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Only models FDT, FDTC, FDTW, FDTS, FDTQ,
FDU, FDUM, FDQS, FDUH
1 cycle time
Stop time
Voltage fluctuation
Phase unbalance
Compressor
stop/start
frequency
Power source
voltage
Voltage drop during start
Dew point temperature 28 or less, relative humidity 80% or less
(FDE, FDK, FDFL, FDFU : Dew point temperature 23 or less, relative humidity 80% or less)
Within 3% of rated voltage
Within 15% of rated voltage
Note () When connecting the indoor unit type FDK, FDFL, FDFU or FDFW (not yet) Series, limit the connectable capacity not higher than 30%.
(2) When the pipe extension length exceeds 50 m, additional refrigerant oil must be charged (,000 cc).
(3) In case of less than 50m, the standard models are applied.
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
First branch
50~100m
(3)
50~100m
(3)
MAX.
90m
(2)
MAX.
40m
(2)
MAX. 90m
MAX. 90m
(2)
MAX. 18m
MAX.
130m
MAX.
130m
MAX. 18m
MAX. 18m
MAX.
40m
(2)
MAX. 18m
MAX. 18m
MAX. 18m
(Lowest indoor unit)
(Highest indoor unit)
(Highest indoor unit)
(Lowest indoor unit)
First branch
(Header)
denotes
System
FDCH615CKXE6G
FDCH680CKXE6G
Refer to page15
2 to 44 unit
2 to 49 unit
1 to 40 unit
Item
Indoor air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Single direction piping length
Actual length : 160m or less, Eguivalent length : 185m or less
Total piping length
(2)
Main pipe length
1000m or less
130m or less
90m or less (However, difference between the longest and shortest piping : 40m or less)
6 min or more (3 minutes or more from start to stop or 3 minutes or more from stop to start)
3 min or more
Within 10% of rated voltage
50~100m
(3)
Prohibited activity
18m or less
Allowable pipe length from the first branching
18m or less
Elevation difference between the first branching point and the indoor unit
Number of connected units
Connectable capacity
(1)
FDCH560CKXE6G
280 ~ 896
308 ~ 984
340 ~ 1088
Outdoor unit is higher
Outdoor unit is lower
Indoor units
that can be
used in
combination
Difference in
height between
indoor and outdoor
units
Difference in the elevation of indoor units in a system
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Only models FDT, FDTC, FDTW, FDTS, FDTQ,
FDU, FDUM, FDQS, FDUH
1 cycle time
Stop time
Voltage fluctuation
Phase unbalance
Compressor
stop/start
frequency
Power source
voltage
Voltage drop during start
Dew point temperature 28 or less, relative humidity 80% or less
(FDE, FDK, FDFL, FDFU : Dew point temperature 23 or less, relative humidity 80% or less)
Within 3% of rated voltage
Within 15% of rated voltage
Summary of Contents for FDCH1010CKXE6G
Page 8: ... 09 KX T 139 2 2 Exterior dimensions Models FDCH335CKXE6G K 400CKXE6G 450CKXE6G PCB003Z141 ...
Page 9: ... 09 KX T 139 Models FDCH504CKXE6G 560CKXE6G 560CKXE6G K 615CKXE6G 680CKXE6G PCB003Z142 ...
Page 10: ... 09 KX T 139 2 3 Electrical wiring Models All model PCB003Z139 ...
Page 41: ......
Page 42: ... 40 09 KX T 139 ...
Page 63: ... 09 KX T 139 Combination use PCB003Z587 61 ...
Page 64: ... 09 KX T 139 2 2 Exterior dimensions Models FDCH335CKXE6G K 400CKXE6G 450CKXE6G PCB003Z589 62 ...
Page 65: ... 09 KX T 139 Models FDCH504CKXE6G 560CKXE6G 560CKXE6G K 615CKXE6G 680CKXE6G PCB003Z590 63 ...
Page 66: ... 09 KX T 139 2 3 Electrical wiring Models All model PCB003Z588 64 ...