-
182
-
Outdoor heat exchanger thermistor : -50°C or lower
Ambient air temperature thermistor : -30°C or lower
Low pressure sensor:
0 V or lower, or 3.49 V or higher.
(ii) Discharge pipe temperature thermistor, suction pipe temperature thermistor, under-dome temperature thermistor. (models
802, 1002 only)
After the compressor goes ON, if the following is detected for 5 seconds continuously between 10 minutes and 10 minutes
20 seconds after the compressor goes ON, the compressor stops. After a 3-minute delay, the compressor is restarted, but
if this state is detected 3 times within a 40-minute period, an anomalous stop occurs.
Note (1) This is not detected during defrosting and for 3 minutes after defrosting.
Discharge pipe temperature thermistor: -10°C or lower
Suction pipe temperature thermistor:
-50°C or lower
Under-dome temperature thermistor:
-50°C or lower
(k) Test
operation
( i ) It is possible to operate the outdoor unit using SW3-3 (SW5-3) and SW3-4 (SW5-4) on the outdoor unit PCB.
Be sure to turn SW3-3 (SW5-3) OFF when operation ends.
(ii) Test operation control
1) The air conditioner is operated at the predetermined maximum speed for each model.
2) Each protective control and anomalous sensing control is activated.
3) If the setting of SW3-4 (SW5-4) is changed during test operation, and the compressor is stopped temporarily, and
operation mode is switched between cooling and heating.
4) Set point and indication on the remote controller follows the below table.
(i)
Silent mode control
Silent operation in done according to the remote control function setting.
( i ) Fan speed is reduced in comparison with normal operation mode specifi ed in item.
1) Fan speed during cooling and dehumidifying operation.
2) Fan speed during heating
(ii) Maximum compressor speed is limited as mentioned in the following table.
(rps)
Model
Mode
302
402
502
602
802
1002
cooling
76
60
80
85
70
80
heating
86
60
80
85
70
80
SW3-3
(SW5-3)
OFF
ON
SW3-4
(SW5-4)
ON
OFF
Cooling test operation
Heating test operation
Normal or test operation end
5ºC
30ºC
Set point
Indication
Mode
Item
Cooling test operation
Heating test operation
Note (1) Values in ( ) show in the case of the 302 model.
TEST RUN
30ºC
5(6)th Speed
5th Speed
4th Speed
3rd Speed
5th Speed
5th Speed
3rd Speed
3rd Speed
5th Speed
3rd Speed
3rd Speed
2nd Speed
4th Speed
3rd Speed
2nd Speed
1st Speed
5th Speed
5th Speed
4th Speed
3rd Speed
5th Speed
5th Speed
3rd Speed
3rd Speed
5th Speed
3rd Speed
3rd Speed
2nd Speed
4th Speed
3rd Speed
2nd Speed
1st Speed
Zone
Zone
Zone
Zone
302 ~ 602 models
802 ~ 1002 models
Note (1) Values in ( ) show in the case of the 302 model.
Zone
Zone
Zone
Zone
Zone
Zone
Zone
Zone
A
B
C
D
Zone
Zone
Zone
Zone
A
B
C
D
3rd Speed
3rd Speed
4th Speed
3rd Speed
3rd Speed
5th Speed
3rd Speed
5th Speed
6th Speed
3rd Speed
3rd Speed
4th Speed
3rd Speed
3rd Speed
5th Speed
3rd Speed
5th Speed
6th Speed
302 ~ 602 models
802 ~ 1002 models
Zone
Zone
Zone
A
B
C
Zone
Zone
Zone
A
B
C
Zone
Zone
Zone
Zone
Zone
Zone