-
20
-
Model FDTVA602HEN2R
Model
Item
FDTVA602HEN2R
FDTA601R
FDCVA602HENAR
Nominal cooling capacity
(1)
kW
14.0 [6.7~14.8]
Nominal heating capacity
(1)
kW
16.0 [6.3~16.8]
Power source
1 Phase, 220-240V 50Hz/220V 60Hz
Operation data
(3)
Cooling power consumption
kW
4.65/4.65
Running current (Cooling)
A
20.4/21.3
Power factor (Cooling)
%
99/99
Heating power consumption
kW
4.54/4.54
Running current (Heating)
A
20.0/20.9
Power factor (Heating)
%
99/99
Inrush current (L.R.A)
A
5
Noise level
dB(A)
Powerful mode Hi:48 Me:45 Lo:43
Mild mode Hi:45 Me:43 Lo:40
53
Exterior dimensions
Height
×
Width
×
Depth
mm
Unit 365 × 840 × 840
Panel 35 × 950 × 950
845 × 970 × 370
Net weight
kg
38 (Unit:31 Panel:7)
74
Refrigerant equipment
Compressor type & Q’ty
–
RM-B5125MDE21 × 1
Starting method
–
Direct line start
Heat exchanger
Louver fin & inner grooved tubing
Straight fin & inner grooved tubing
Refrigerant control
–
Electronic expansion valve
Refrigerant
R410A
Quantity
kg
–
3.8 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
0.7 (M-MA68)
Defrost control
Microcomputer controlled de-icer
Air handling equipment
Fan type & Q’ty
Turbo fan
×
1
Propeller fan
×
1
Motor
W
120
×
1
120
×
1
Starting method
Direct line start
Direct line start
Air fl ow
CMM
Powerful mode Hi:34 Me:30 Lo:26
Mild mode Hi:30 Me:26 Lo:23
Cooling: 75, Heating: 73
Outside air intake
Available
–
Air filter, Q’ty
Plastic net (washable) × 1
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
20 (Crank case heater)
Operation control
Operation switch
Wired remote control switch (Optional : RC-E1R)
Wireless kit (Optional : RCN-T-35W-ER)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
Installation data
Refrigerant piping size
mm
(in)
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
15.88 (5/8
″
)
Connecting method
Flare piping
Drain hose
Connectable with VP25 (I.D. 25mm, O.D. 32mm)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose
Optional parts
Decorative Panel (T-PSA-35W-ER)
Notes (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO-T1
Heating
20˚C
–
7˚C
6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
(4) Values in [ ~ ] show the minimum to maximum range.