232
-
12
Function No. A
(Example) If the upper limit is set at 28
˚
C
Function Contents B
Setting Contents ˚C
TEMP RANGE SET
DISP CHANGE
NO DISP CHANGE
Control Contents
The remote controller’s display and sent
data upper limit changes to 28 ˚C.
The remote controller’s display upper
limit remains at 30 ˚C and only the upper
limit of the sent data is changed to 28 ˚C.
• If
the RESET button is pressed during a setting operation, the display returns to the previously displayed setting screen.
However, settings which have not been fi xed become invalid, so exercise caution.
* If “NO DISP CHANGE” is selected in No. 12, “TEMP RANGE SET” of the remote controller’s functions, of the func-
tion setting modes, the remote controller’s display does not change even if the temperature range has been changed.
Pressing the RESET button during remote controller unit operation will undo your last operation and allow you to go back
to the previous screen.
(8) Checking operation data
Operation data can be checked with remote controller unit operation.
Press the CHECK button.
The display change from “
SELECT ITEM”
“
SET”
“OPERATION DATA
”.
Press the SET button while “OPERATION DATA
” is displayed.
The display will change to “I/U No. 00
” (blinking indication).
Select the indoor unit number you want to have data displayed with the
button.
(When only one indoor unit connected, the indoor unit number displayed on the screen will not change.)
Determine the indoor unit number with the SET button.
(The indoor unit number changes from blinking indication to continuous indication.)
“DATA LOADING” (A blinking indication appears while data is loaded)
“OPERATION DATA ” appears and data number 01 is displayed.
Upon operation of the
button, the current operation data is displayed in order from Data number 01.
The items displayed are as follows:
* Depending on models, the items that do not have corresponding data are not displayed.
To display the data of a different indoor unit, press the AIR CON No. button, which allows you to go back to the indoor unit
selection screen.
Pressing the ON/OFF button will stop displaying data.