5) The state of the electronic expansion valve.
The following table illustrates the steady states of the electronic expansion valve.
1)
Cooling test operation procedure
Operate the remote control unit as follows.
a) Starting the cooling test operation
Start the system by pressing the ON/OFF button.
Select “
(COOL)” with the MODE button.
Press the TEST button for 3 seconds or longer.
The screen display will be switched as follows “
SELECT ITEM” “
SET” “ TEST RUN
”.
When the SET button is pressed while “
TEST RUN
” is indicated, a cooling test run will start.
The screen display will pressed to “
TEST RUN.”
b) Ending a cooling test run
Pressing the ON/OFF button or the TEMP
button will end a cooling test run.
“
TEST RUN” shown on the screen will go off.
(b) Test run from an wired remote controller.