285
-
Indoor unit
Red LED
Green LED
Stays OFF
Keeps flashing
Red LED
1 time, 2 time, 3 time flash
Outdoor unit
NO
NO
NO
NG
YES
Check the power supply
Replace the compressor
Replace the compressor.
OK
Check the refrigerant amount
and refrigerant circuit.
Inverter
NG
Inverter
OK
Check
the compressor
insulation resistance
and winding
resistance.
Is the balance
pressure appropriate
during starting?
Is the power
supply voltage
proper?
(1)
YES
Carry out test operation
(starting) another 2 or 3 times.
Does the
compressor start?
Replace the
control PCB
Check the
power transistor
module (Reference
to 287)
22
[Anomaly in compressor starting]
Error display :
E59
•
Display conditions
(1) The error occurs when the compressor wouldn’t operate after
attempting to start 2 times by 7 times.
(2) Remote controller reset is possible after 3 minutes have passed.
Note (1) If the test operation is repeated 2 or 3 times, the liquid
refrigerant inside the compressor may be expelled from the
compressor may recover from its starting anomaly.
• Models FDCVA151~251
Indoor unit
Red LED
Green LED
Stays OFF
Keeps flashing
Red LED
Green LED
5 time flash
Keeps flashing
Outdoor unit
NO
NO
NO
NO
YES
Check the power supply
Replace the compressor
Replace the compressor.
OK
Check the refrigerant amount
and refrigerant circuit.
Inverter
NG
Inverter
OK
Check
the compressor
insulation resistance
and winding
resistance.
(0)
Is the balance
pressure appropriate
during starting?
Is the power
supply voltage
proper?
(2)
YES
Carry out test operation
(starting) another 2 or 3 times.
Does the
compressor
start?
Replace the outdoor
unit inverter PCB
YES
NO
In case the compressor
wouldn't start at all, and
there is not even slight
vibration or noise.
Disconnect the outdoor
unit fan motor and run
the system.
To the following flow
chart.
Replace the outdoor unit fan motor.
Compressor starts?
Check the
power transistor
module (Refer
to 287)
•
Display conditions
(1) The error occurs when the compressor wouldn’t operate after
attempting to start 10 times by 2 sets.
(2) Remote controller reset is possible after 3 minutes have passed.
Notes (1) The winding resistance is 0.4
Ω
or more at 25°C.
(2) If the test operation is repeated 2 or 3 times, the liquid
refrigerant inside the compressor may be expelled from
the compressor may recover from its starting anomaly.
Note (1) Check if the power supply system is normal.
• Models FDCVA302~1002