286
-
NO (E59)
(1)
YES
YES
E59 diagnosis
E42 diagnosis
Check the
compressor
It doesn’t
recur.
E60 recurs.
Does the
compressor make
any anomalous
noise?
Does it
return to normal
when the power
is reset?
Does E42 occur?
YES
NO
NO
Replace the outdoor
unit inverter PCB
It is possible that
transient noise
could be causing
malfunction. If
there is a noise
source, take coun-
termeasures to
prevent it.
Operate the
system again
Does the compressor
start?
Indoor unit
Red LED
Green LED
Stays OFF
Keeps flashing
Red LED
1 time flash
Keep flashing
Outdoor unit
23
[Compressor loader position detection error]
[Only case of 151 ~ 251, 802, 1002 models]
Error display :
E60
Note (1) Check if the power supply system is normal.
•
Display conditions
(1) The error occurs when the rotor position cannot be detected 4 times within 15 minutes after once it is detected.
(2) After 3 minutes passes, it is reset with the remote controller is possible.
Note (1) Replace the power
transistor.