(6) Check anomalous operation data with the wired remote controller
Operation data are recorded when there is an anomalous state and these data can be displayed in the remote controller by
operating the remote controller buttons.
(1) Press the CHECK button.
The display will change from “
FUNCTION”
→
“
SET ”
→
“OPERATION DATA
”
(2) Press
the
button once. The display will change to “ERROR DATA
”.
(3) Press the SET button to enter the anomalous operation data display mode.
(4) If there are anomalous from the past, they will be displayed by an error code and unit No.
(Example) “E8” (Lighted up)
“I/U No. 00
” (Flashing)
(5) Using
the
or
button, select the indoor unit No. you want to display the error data for.
If only one indoor unit is connected, the indoor unit No. does not change.
(6) Fix the selection using the SET button. (The displayed indoor unit No. will change from fl ashing to light up continu-
ously.)
(Example) “E8”
“DATA LOADING” (This message fl ashes while data are being read.)
↓
“E8”
“ERROR
DATA
”
The data are then displayed beginning with item No. 01.
Displayed items are as shown below.
(7) Display the other data for when the error occurred in order from the currently displayed operation data No. 01 using
the
or
button.
*
Depending on the model, items for which corresponding data do not exist are not displayed.
(8) To change the indoor unit, press the AIR CON No. button and return to the indoor unit selection display.
(9) Press the ON/OFF button to end the anomalous operation data check.
If you press the RESET button during the settings, the display returns to the previous setting screen.
No.
Data item
01
(Operation mode)
02
SET TEMP
03
RETURN AIR
04
I/U HEAT EXCH1
05
I/U HEAT EXCH2
07
I/U FAN
11
TOTAL I/U RUN
21
OUTDOOR
22
O/U HEAT EXCH1
23
O/U HEAT EXCH2
24
COMP HERTZ
26
Lo PRESSURE
27
DISCHARGE
28
DOME BOTTOM
29
CT
31
O/U FAN
32
SILENT MODE ON/OFF
34
63H1 ON/OFF
35
DEFROST ON/ OFF
36
TOTAL COMP RUN
37
EEV1