308
-
Models FDCVA502HENAR, 602HENAR
Item
kW
kW
kg
RM-B5125MDE21 1
74
dB(A)
W
kg
W
CMM
Cooling: 75, Heating: 73
mm(in)
mm
Model
FDCVA602HENAR
FDCVA502HENAR
12.5 [6.5~14.0]
14.0 [6.2~16.0]
1 Phase, 220-240V 50Hz/220V 60Hz
Direct line start
Direct line start
Flare piping
Necessary (both Liquid & Gas lines)
52
14.0 [6.7~14.8]
16.0 [6.3~16.8]
53
0.7 (M-MA68)
3.8 (Pre-charged up to the piping length of 30m)
20
R410A
845 970 370
Nominal cooling capacity
(1)
Power source
Nominal heating capacity
(1)
Net weight
Crankcase heater
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
Starting method
Exterior dimensions
Height Width Depth
Refrigerant equipment
compressor type & Q' ty
Noise level
(1) The cooling and heating capabilities imply the values when the indoor unit of rated capacity is connected under the condition specified in ISO-T1.
(2) The refrigerant quantity in the connecting pipe is not included. Charge it additionally at the site.
Notes
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow(Standard)
Shock & vibration absorber
Rubber mount (for compressor)
Internal thermostat for fan motor.
Abnormal discharge temperature protection.
Safety equipment
Connecting method
Drain
Insulation for piping
Accessories
Installation data
Refrigerant piping size
Electronic expansion valve
Microcomputer controlled de-icer
Straight fin & inner grooved tubing
Propeller fan 1
120 1
Hole for drain ( 20 3pcs.)
Liquid line: 9.52 (3/8") Gas line: 15.88 (5/8")
Edging
(3) Values in [ ~ ] show the minimum and maximum capacities.