310
-
Model FDCVA802HESAR, 1002HESAR
Item
kW
kW
kg
122
140
dB(A)
W
kg
W
CMM
Cooling: 150, Heating: 145
mm(in)
mm
Model
FDCVA1002HESAR
FDCVA802HESAR
20.0 [7.0~22.4]
22.4 [7.6~25.0]
3 Phase, 380-415V 50Hz/380V 60Hz
Direct line start
40
Direct line start
Liquid line: Flare piping, Gas line: Brazing
Reducer kit (Please see page 218), Accessory pipe (Please see page 220)
Necessary (both Liquid & Gas lines)
25.0 [10.6~28.0]
28.0 [9.5~31.5]
57
Cooling: 57, Heating: 58
5.4
(Pre-charged up to the piping length of 30m)
7.2
(Pre-charged up to the piping length of 30m)
R410A
1.45 (M-MA32R)
1300 970 370
1505 970 370
Nominal cooling capacity
(1)
Power source
Nominal heating capacity
(1)
Net weight
Crankcase heater
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
Starting method
Exterior dimensions
Height Width Depth
Refrigerant equipment
compressor type & Q' ty
Noise level
(1) The cooling and heating capabilities imply the values when the indoor unit of rated capacity is connected under the condition specified in ISO-T1.
(2) The refrigerant quantity in the connecting pipe is not included. Charge it additionally at the site.
Notes
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow(Standard)
Shock & vibration absorber
Rubber mount (for compressor)
Internal thermostat for fan motor.
Abnormal discharge temperature protection.
Safety equipment
Connecting method
Drain
Insulation for piping
Accessories
Installation data
Refrigerant piping size
Electronic expansion valve
Microcomputer controlled de-icer
Straight fin & inner grooved tubing
Propeller fan 2
120 2
Hole for drain ( 20 6pcs.)
Liquid line: 9.52 (3/8")
Gas line: 25.4 (1")
Liquid line: 12.7 (1/2")
Gas line: 25.4 (1")
GT-C5150ND79 1
(3) Values in [ ~ ] show the minimum and maximum capacities.