36
-
(3) Ceiling suspended type (FDEN)
(a) Single
type
Model FDENVA151HEN1R
Model
Item
FDENVA151HEN1R
FDENA151R
FDCVA151HENR
Nominal cooling capacity
(1)
kW
3.8 [1.8~4.7]
Nominal heating capacity
(1)
kW
4.5 [2.0~5.4]
Power source
1 Phase, 220-240V 50Hz/220V 60Hz
Operation data
(3)
Cooling power consumption
kW
1.18/1.18
Running current (Cooling)
A
5.3/5.5
Power factor (Cooling)
%
97/98
Heating power consumption
kW
1.32/1.32
Running current (Heating)
A
5.9/6.2
Power factor (Heating)
%
97/97
Inrush current (L.R.A)
A
5
Noise level
dB(A)
Powerful mode Hi:42 Me:39 Lo:38
Mild mode Hi:39 Me:38 Lo:37
48
Exterior dimensions
Height
×
Width
×
Depth
mm
210 × 1070 × 690
595 × 780 (+67) × 290
Net weight
kg
30
40
Refrigerant equipment
Compressor type & Q’ty
–
5CS102XFD × 1
Starting method
–
Direct line start
Heat exchanger
Louver fin & inner grooved tubing
Straight fin & inner grooved tubing
Refrigerant control
–
Electronic expansion valve
Refrigerant
R410A
Quantity
kg
–
1.55 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
0.48 (RB68A)
Defrost control
Microcomputer controlled de-icer
Air handling equipment
Fan type & Q’ty
Multiblade centrifugal fan × 2
Propeller fan
×
1
Motor
W
30
×
1
34
×
1
Starting method
Direct line start
Direct line start
Air fl ow
CMM
Powerful mode Hi:12 Me:11 Lo:9
Mild mode Hi:11 Me:9 Lo:7
41
Outside air intake
Unavailable
–
Air filter, Q’ty
Plastic net (washable) × 2
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
20 (Crank case heater)
Operation control
Operation switch
Wireless remote control switch (Optional: RCN-E1R)
Wired remote control switch (Optional: RC-E1R)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
Installation data
Refrigerant piping size
mm
(in)
Liquid line:
φ
6.35 (1/4
″
) Gas line:
φ
12.7 (1/2
″
)
Connecting method
Flare piping
Drain hose
Connectable with VP20 (I.D.20mm, O.D.26mm)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose
Optional parts
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO-T1
Heating
20˚C
–
7˚C
6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
(4) Values in [ ~ ] show the minimum to maximum range.