54
-
Model FDENVA1002HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)
Model
Item
FDENVA1002HESP2R
FDENA501R
FDCVA1002HESAR
Nominal cooling capacity
(1)
kW
25.0 [10.6~28.0]
Nominal heating capacity
(1)
kW
28.0 [9.5~31.5]
Power source
3 Phase, 380-415V 50Hz/380V 60Hz
Operation data
(3)
Cooling power consumption
kW
9.01/9.01
Running current (Cooling)
A
13.5/14.1
Power factor (Cooling)
%
96/97
Heating power consumption
kW
8.05/8.05
Running current (Heating)
A
12.2/12.8
Power factor (Heating)
%
95/96
Inrush current (L.R.A)
A
5
Noise level
dB(A)
Powerful mode Hi:48 Me:46 Lo:44
Mild mode Hi:46 Me:44 Lo:43
Cooling:57, Heating:58
Exterior dimensions
Height
×
Width
×
Depth
mm
250 × 1620 × 690
1505 × 970 × 370
Net weight
kg
46
140
Refrigerant equipment
Compressor type & Q’ty
–
GT-C5150ND79 × 1
Starting method
–
Direct line start
Heat exchanger
Louver fin & inner grooved tubing
Straight fin & inner grooved tubing
Refrigerant control
–
Electronic expansion valve
Refrigerant
R410A
Quantity
kg
–
7.2 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
1.45 (M-MA32R)
Defrost control
Microcomputer controlled de-icer
Air handling equipment
Fan type & Q’ty
Multiblade centrifugal fan × 4
Propeller fan
×
2
Motor
W
45
×
2
120
×
2
Starting method
Direct line start
Direct line start
Air fl ow
CMM
Powerful mode Hi:31 Me:29 Lo:26
Mild mode Hi:29 Me:26 Lo:23
Cooling: 150, Heating: 145
Outside air intake
Unavailable
–
Air filter, Q’ty
Plastic net (washable) × 2
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
40 (Crank case heater)
Operation control
Operation switch
Wireless remote control switch (Optional: RCN-E1R)
Wired remote control switch (Optional: RC-E1R)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
Installation data
Refrigerant piping size
Liquid line
mm
(in)
Indoor branch pipe:
φ
9.52 (3/8
″
), Outdoor main pipe:
φ
12.7 (1/2
″
)
Gas line
(7)
Indoor branch pipe:
φ
15.88 (5/8
″
), Outdoor main pipe:
φ
25.4 (1
″
)
Connecting method
Flare piping (Outdoor gas piping: Brazing)
Drain hose
Connectable with VP20 (I.D. 20mm, O.D. 26mm)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose, Reducer kit, (Please see page 218), Accessory pipe (Please see page 220)
Optional parts
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO-T1
Heating
20˚C
–
7˚C
6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
(5) Indoor unit specifications show the specifications for one unit. Capacity and running characteristics values are shown for the case where two indoor
units are combined and run together.
(6) If wireless specifications are used, use 1 wireless indoor unit in combination with wired indoor units.
(7) Be sure to use the accessory pipe to connect service valve on the gas side with the fi eld pipe.(Refer to the 220 page).