62
-
Model FDUMVA402HES2R
Model
Item
FDUMVA402HES2R
FDUMA402R
FDCVA402HESAR
Nominal cooling capacity
(1)
kW
10.0 [6.1~11.2]
Nominal heating capacity
(1)
kW
11.2 [6.0~12.5]
Power source
3 Phase, 380-415V 50Hz/380V 60Hz
Operation data
(3)
Cooling power consumption
kW
2.80/2.80
Running current (Cooling)
A
4.2/4.4
Power factor (Cooling)
%
96/97
Heating power consumption
kW
2.77/2.80
Running current (Heating)
A
4.1/4.3
Power factor (Heating)
%
98/99
Inrush current (L.R.A)
A
5
Noise level
dB(A)
Hi:37 Me:35 Lo:32
50
Exterior dimensions
Height
×
Width
×
Depth
mm
350 × 1370 × 635
845 × 970 × 370
Net weight
kg
59
74
Refrigerant equipment
Compressor type & Q’ty
–
RM-B5125MDE31 × 1
Starting method
–
Direct line start
Heat exchanger
Louver fin & inner grooved tubing
Straight fin & inner grooved tubing
Refrigerant control
–
Electronic expansion valve
Refrigerant
R410A
Quantity
kg
–
3.8 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
0.7 (M-MA68)
Defrost control
Microcomputer controlled de-icer
Air handling equipment
Fan type & Q’ty
Multiblade centrifugal fan × 3
Propeller fan
×
1
Motor
W
45
×
1, 90
×
1
120
×
1
Starting method
Direct line start
Direct line start
Air fl ow (Standard)
CMM
Hi: 28 Me: 25 Lo: 22
Cooling type: 75, Heating type: 73
Available static pressure
Pa
Standard: 60, Max: 90
–
Outside air intake
–
–
Air filter, Q’ty
–
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
20 (Crank case heater)
Operation control
Operation switch
Wired remote control switch (Optional : RC-E1R)
Wireless kit (Optional : RCND-KIT-HER)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
Installation data
Refrigerant piping size
mm
(in)
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
15.88 (5/8
″
)
Connecting method
Flare piping
Drain hose
Connectable with VP25 (I.D. 25mm, O.D. 32mm)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose
Optional parts
Filter kit (UM-FL3E)
Notes (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO-T1
Heating
20˚C
–
7˚C
6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
(4) Values in [ ~ ] show the minimum to maximum range.