-
76
-
Model FDUMVA602HEST2R(Indoor unit: 3 units, Outdoor unit: 1 unit)
Model
Item
FDUMVA602HEST2R
FDUMA202R
FDCVA602HESAR
Nominal cooling capacity
(1)
kW
14.0 [6.7~14.5]
Nominal heating capacity
(1)
kW
16.0 [6.3~16.5]
Power source
3 Phase, 380-415V 50Hz/380V 60Hz
Operation data
(3)
Cooling power consumption
kW
5.09/5.09
Running current (Cooling)
A
7.4/7.8
Power factor (Cooling)
%
99/99
Heating power consumption
kW
4.89/4.89
Running current (Heating)
A
7.1/7.5
Power factor (Heating)
%
99/99
Inrush current (L.R.A)
A
5
Noise level
dB(A)
Hi:34 Me:31 Lo:28
53
Exterior dimensions
Height
×
Width
×
Depth
mm
299 × 750 × 635
845 × 970 × 370
Net weight
kg
34
74
Refrigerant equipment
Compressor type & Q’ty
–
RM-B5125MDE31 × 1
Starting method
–
Direct line start
Heat exchanger
Louver fin & inner grooved tubing
Straight fin & inner grooved tubing
Refrigerant control
–
Electronic expansion valve
Refrigerant
R410A
Quantity
kg
–
3.8 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
0.7 (M-MA68)
Defrost control
Microcomputer controlled de-icer
Air handling equipment
Fan type & Q’ty
Multiblade centrifugal fan
×
2
Propeller fan
×
1
Motor
W
55
×
1
120
×
1
Starting method
Direct line start
Direct line start
Air fl ow (Standard)
CMM
Hi:14 Me:12 Lo:11
Cooling:75, Heating:73
Available static pressure
Pa
Standard:50, Max:85
–
Outside air intake
–
–
Air filter, Q’ty
–
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
20 (Crank case heater)
Operation control
Operation switch
Wired remote control switch (Optional : RC-E1R)
Wireless kit (Optional : RCND-KIT-HER)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
Installation data
Refrigerant piping size
Liquid line
mm
(in)
Indoor branch pipe, Outdoor main pipe:
φ
9.52 (3/8
″
)
Gas line
Indoor branch pipe:
φ
12.7 (1/2
″
), Outdoor main pipe:
φ
15.88 (5/8
″
)
Connecting method
Flare piping
Drain hose
Connectable with VP25 (I.D. 25mm, O.D. 32mm)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose
Optional parts
Filter kit (UM-FL3E)
Notes (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO-T1
Heating
20˚C
–
7˚C
6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1
“UNITARY
AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
(5) Indoor unit specifications show the specifications for one unit. Capacity and running characteristics values are shown for the case where three indoor
units are combined and run together.