125
-
Preset point of the protective devices
Parts name
Mark
Equipped
unit
152, 202, 252 model
302, 402, 502, 602 model
802, 1002 model
Thermistor
(for protection over-
loading in heating)
Th
I
-R
Indoor unit
OFF 63˚C
ON 56˚C
Thermistor
(for frost prevention)
OFF 1.0˚C
ON 10˚C
Thermistor
(for detecting dis-
charge pipe temp.)
Tho-D
Outdoor unit
OFF 105˚C
ON 80˚C
OFF 115˚C
ON 85˚C
OFF 135˚C
ON 90˚C
High pressure switch
(for protection)
63H1
Outdoor unit
—
OFF 4.15MPa
ON 3.15MPa
Low pressure sensor
(for protection)
LPT
Outdoor unit
—
OFF 0.227MPa
ON 0.079MPa