239
-
Outdoor unit LED
Indoor unit LED
Green
K
eeps flashing
K
eeps flashing
K
eeps flashing
K
eeps flashing
K
eeps flashing
K
eeps flashing
K
eeps flashing
K
eeps flashing
K
eeps flashing
K
eeps flashing
K
eeps flashing
K
eeps flashing
K
eeps flashing
K
eeps flashing
Red
Green
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
Stays OFF
1 time flash
1 time flash
1 time flash
1 time flash
1 time flash
1 time flash
1 time flash
Red
Outdoor unit po
wer supply open phase, Noise f
ilter defect (FDCV
A302~1002)
Dischar
ge temperature anomaly
.
Dischar
ge pipe thermistor f
ailure
63H1 operation, Operation with service v
alv
e closed (FDCV
A302~1002)
Ambient air temperature thermistor f
ailure
DC f
an motor anomalous.
Remote
contr
oller
err
or code
E34
K
eeps flashing
Stays OFF
1 time flash
In
v
erter primary side current is anomalous (FDCV
A151~251)
E33
E36
E37
E38
E39
E40
E48
Cause
K
eeps flashing
K
eeps flashing
Stays OFF
1 time flash
E35
K
eeps flashing
Stays OFF
1 time flash
Current (Anomaly in a compressor o
v
er current), Operation with service v
alv
e closed
E42
K
eeps flashing
K
eeps flashing
Stays OFF
1 time flash
Po
wer transistor o
v
erheat (FDCV
A402~1002)
E41
K
eeps flashing
K
eeps flashing
K
eeps flashing
Stays OFF
1 time flash
In
v
erter communications error (FDCV
A302~1002)
E45
K
eeps flashing
K
eeps flashing
Stays OFF
1 time flash
In
v
erter o
v
er
-v
oltage trouble (FDCV
A151~251)
In
v
erter
A/F module o
v
ercurrent trouble (FDCV
A302)
E47
K
eeps flashing
K
eeps flashing
Stays OFF
1 time flash
Lo
w pressure anomalous or lo
w pressure sensor disconnected (FDCV
A302~1002)
E49
K
eeps flashing
K
eeps flashing
Stays OFF
1 time flash
In
v
erter PCB anomalous (FDCV
A302~1002)
E51
K
eeps flashing
K
eeps flashing
Stays OFF
1 time flash
Suction pipe temperature thermistor disconnected (FDCV
A302~1002)
E53
K
eeps flashing
K
eeps flashing
Stays OFF
1 time flash
Lo
w pressure sensor disconnected or anomalous (FDCV
A302~1002)
E54
K
eeps flashing
K
eeps flashing
Stays OFF
1 time flash
Compressor under
-dome temperature thermistor disconnected (FDCV
A802,1002)
Compressor startup error (FDCV
A151~251)
E55
K
eeps flashing
K
eeps flashing
Stays OFF
1 time flash
1 time flash
2 time flash
3 time flash
Insuf
ficient refrigerant (FDCV
A151~251, 402~1002)
E57
K
eeps flashing
Stays OFF
1 time flash
Po
wer transistor thermistor is f
aulty or disconnection or connector connections are
poor (FDCV
A151~251)
E56
K
eeps flashing
K
eeps flashing
5 time flash
K
eeps flashing
Stays OFF
Compressor startup error (FDCV
A302~1002)
E59
K
eeps flashing
Stays OFF
1 time flash
Compressor rotor position detection error (FDCV
A151~251)
E60
Outdoor unit heat e
xchanger thermistor
failure
Outdoor heat e
xchanger temperature is high or outdoor heat e
xchanger thermistor
is f
aulty
.
2)
Outdoor unit side
Note (1)
The green LED in the outdoor unit is used in the FDCV
A302~1002 models.