38
-
Model FDENVA251HEN1R
Model
Item
FDENVA251HEN1R
FDENA251R
FDCVA251HENR
Nominal cooling capacity
(1)
kW
5.6 [2.8~6.3]
Nominal heating capacity
(1)
kW
6.7 [3.1~7.1]
Power source
1 Phase, 220-240V 50Hz/220V 60Hz
Operation data
(3)
Cooling power consumption
kW
1.74/1.74
Running current (Cooling)
A
7.8/8.2
Power factor (Cooling)
%
97/96
Heating power consumption
kW
1.87/1.87
Running current (Heating)
A
8.3/8.7
Power factor (Heating)
%
98/98
Inrush current (L.R.A)
A
5
Noise level
dB(A)
Powerful mode Hi:44 Me:41 Lo:39
Mild mode Hi:41 Me:39 Lo:38
48
Exterior dimensions
Height
×
Width
×
Depth
mm
210 × 1320 × 690
595 × 780 (+67) × 290
Net weight
kg
36
40
Refrigerant equipment
Compressor type & Q’ty
–
5CS102XFD × 1
Starting method
–
Direct line start
Heat exchanger
Louver fin & inner grooved tubing
Straight fin & inner grooved tubing
Refrigerant control
–
Electronic expansion valve
Refrigerant
R410A
Quantity
kg
–
1.75 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
0.48 (RB68A)
Defrost control
Microcomputer controlled de-icer
Air handling equipment
Fan type & Q’ty
Multiblade centrifugal fan
×
4
Propeller fan
×
1
Motor
W
20
×
2
34
×
1
Starting method
Direct line start
Direct line start
Air fl ow
CMM
Powerful mode Hi:20 Me:18 Lo:14
Mild mode Hi:18 Me:14 Lo:12
41
Outside air intake
Unavailable
–
Air filter, Q’ty
Plastic net (washable) × 2
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
20 (Crank case heater)
Operation control
Operation switch
Wireless remote control switch (Optional: RCN-E1R)
Wired remote control switch (Optional: RC-E1R)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
Installation data
Refrigerant piping size
mm
(in)
Liquid line:
φ
6.35 (1/4
″
) Gas line:
φ
15.88 (5/8
″
)
Connecting method
Flare piping
Drain hose
Connectable with VP20 (I.D.20mm, O.D.26mm)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose
Optional parts
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO-T1
Heating
20˚C
–
7˚C
6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
Summary of Contents for FDCVA1002HESAR
Page 107: ... 106 60 17 150 b Wireless remote controller Unit mm ...
Page 119: ... 118 Model FDCVA1002HESAR Polar white ...
Page 133: ......