40
-
Model FDENVA402HEN2R
Model
Item
FDENVA402HEN2R
FDENA401R
FDCVA402HENAR
Nominal cooling capacity
(1)
kW
10.0 [6.1~11.2]
Nominal heating capacity
(1)
kW
11.2 [5.9~12.5]
Power source
1 Phase, 220-240V 50Hz/220V 60Hz
Operation data
(3)
Cooling power consumption
kW
2.85/2.85
Running current (Cooling)
A
12.5/13.1
Power factor (Cooling)
%
99/99
Heating power consumption
kW
2.97/2.97
Running current (Heating)
A
13.0/13.6
Power factor (Heating)
%
99/99
Inrush current (L.R.A)
A
5
Noise level
dB(A)
Powerful mode Hi:46 Me:44 Lo:41
Mild mode Hi:44 Me:41 Lo:39
50
Exterior dimensions
Height
×
Width
×
Depth
mm
250 × 1620 × 690
845 × 970 × 370
Net weight
kg
46
74
Refrigerant equipment
Compressor type & Q’ty
–
RM-B5125MDE21 × 1
Starting method
–
Direct line start
Heat exchanger
Louver fin & inner grooved tubing
Straight fin & inner grooved tubing
Refrigerant control
–
Electronic expansion valve
Refrigerant
R410A
Quantity
kg
–
3.8 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
0.7 (M-MA68)
Defrost control
Microcomputer controlled de-icer
Air handling equipment
Fan type & Q’ty
Multiblade centrifugal fan × 4
Propeller fan × 1
Motor
W
40 × 2
120 × 1
Starting method
Direct line start
Direct line start
Air fl ow
CMM
Powerful mode Hi:29 Me:26 Lo:23
Mild mode Hi:26 Me:23 Lo:21
Cooling: 75, Heating: 73
Outside air intake
Unavailable
–
Air filter, Q’ty
Plastic net (washable) × 2
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
20 (Crank case heater)
Operation control
Operation switch
Wireless remote control switch (Optional: RCN-E1R)
Wired remote control switch (Optional: RC-E1R)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
Installation data
Refrigerant piping size
mm
(in)
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
15.88 (5/8
″
)
Connecting method
Flare piping
Drain hose
Connectable with VP20 (I.D.20mm, O.D.26mm)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose
Optional parts
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO-T1
Heating
20˚C
–
7˚C
6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
Summary of Contents for FDCVA1002HESAR
Page 107: ... 106 60 17 150 b Wireless remote controller Unit mm ...
Page 119: ... 118 Model FDCVA1002HESAR Polar white ...
Page 133: ......